Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
12.2.4.2
Table 222:
SXSWI Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
SuppressMidPos
Disabled
Enabled
12.2.5
12.2.5.1
12.2.5.2
12.2.5.3
Technical manual

Settings

Unit
Step
s
0.001
s
0.001
-
-
s
0.001
s
0.001
-
-
-
-
Bay control QCBAY
Identification
Function description
Bay control
Functionality
The Bay control QCBAY function is used together with Local remote and local remote
control functions to handle the selection of the operator place per bay. QCBAY also
provides blocking functions that can be distributed to different apparatuses within the bay.
Function block
QCBAY
LR_OFF
PSTO
LR_LOC
UPD_BLKD
LR_REM
CMD_BLKD
LR_VALID
LOC
BL_UPD
REM
BL_CMD
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 170:
QCBAY function block
Default
Description
3.000
Supervision time for the apparatus to move
after a command
15.000
Allowed time for intermediate position
Not adaptive
Output resets when a new correct end position
is reached
0.200
Output pulse length for open command
0.200
Output pulse length for close command
Disconnector
1=LoadBreak,2=Disconnector,3=GroundSw,
4=HighSpeedGroundSw
Enabled
Mid-position is suppressed during the time
tIntermediate
IEC 61850
IEC 60617
identification
identification
QCBAY
-
Section 12
Control
ANSI/IEEE C37.2
device number
-
367