1MRK 502 048-UUS A
14.4.7
Technical manual
In order to capture the new disturbance it is possible to allow retriggering (PostRetrig =
Enabled) during the post-fault time. In this case a new, complete recording will start and,
during a period, run in parallel with the initial recording.
When the retrig parameter is disabled (PostRetrig = Disabled), a new recording will not
start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a new trig
occurs during the post-fault period and lasts longer than the proceeding recording a new
complete recording will be started.
Disturbance report function can handle maximum 3 simultaneous disturbance recordings.

Technical data

Table 398:
DRPRDRE technical data
Function
Current recording
Voltage recording
Pre-fault time
Post-fault time
Limit time
Maximum number of recordings
Time tagging resolution
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of phasors in the Trip
Value recorder per recording
Maximum number of indications in a
disturbance report
Maximum number of events in the Event
recording per recording
Maximum number of events in the
Sequence of events
Maximum total recording time (3.4 s
recording time and maximum number of
channels, typical value)
Sampling rate
Recording bandwidth
Range or value
-
-
(0.05–3.00) s
(0.1–10.0) s
(0.5–8.0) s
100, first in - first out
1 ms
30 + 10 (external + internally
derived)
96
30
96
150
1000, first in - first out
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
1 kHz at 50 Hz
1.2 kHz at 60 Hz
(5-300) Hz
Section 14
Monitoring
Accuracy
± 1,0% of I
at I ≤ I
r
r
± 1,0% of I at I > Ir
± 1,0% of V
at V≤ V
n
n
± 1,0% of Vat V> V
n
-
-
-
-
See time synchronization
technical data
-
-
-
-
-
-
-
-
-
575