External Polarizing For Ground-Fault Function - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
8.2.7.3
Technical manual
2
×
Ipol = (IA+alpha
IB+alpha IC)/3
ANSIEQUATION2406 V2 EN
where:
IA, IB and IC are fundamental frequency phasors of three individual phase currents.
alpha
phasor with an angle of 120 degrees.
The polarizing current is pre-processed by a discrete fourier filter. Thus the phasor of the
fundamental frequency component of the polarizing current is derived. This phasor is then
multiplied with pre-set equivalent zero-sequence source Impedance in order to calculate
equivalent polarizing voltage VIPol in accordance with the following formula:
(
=
×
=
+ ×
V
Zo
I
RNPol
S
Pol
IPol
EQUATION2013-ANSI V1 EN
which will be then used, together with the phasor of the operating directional current, in
order to determine the direction to the ground fault (Forward/Reverse).
In order to enable current polarizing the magnitude of polarizing current shall be bigger
than a minimum level defined by setting parameter IPolMin.
Dual polarizing
When dual polarizing is selected the function will use the vectorial sum of the voltage
based and current based polarizing in accordance with the following formula:
+
VTotPol=VVPol VIPol=VPol
ANSIEQUATION2408 V1 EN
Vpol and Ipol can be either zero sequence component or negative sequence component
depending upon the user selection.
Then the phasor of the total polarizing voltage VTotPol will be used, together with the
phasor of the operating current, to determine the direction of the ground fault (Forward/
Reverse).

External polarizing for ground-fault function

The individual steps within the protection can be set as non-directional. When this setting
is selected it is then possible via function binary input BLKn(where x indicates the
relevant step within the protection) to provide external directional control (that is, torque
control) by for example using one of the following functions if available in the IED:
×
)
×
I
j XNPOL
Pol
(
+
×
=
+
Z
IPol VPol
RNPol
0s
Section 8
Current protection
)
+
×
jXNPol Ipol
(Equation 52)
(Equation 53)
(Equation 54)
213