Negative-sequence time overcurrent protection for
machines NS2PTOC (46I2)
Identification
Function description
Negative sequence time overcurrent
protection for machines
Functionality
Negative-sequence time overcurrent protection for machines NS2PTOC (46I2) is
intended primarily for the protection of generators against possible overheating of the
rotor caused by negative sequence current in the stator current.
The negative sequence currents in a generator may, among others, be caused by:
Unbalanced loads
Line to line faults
Line to ground faults
Broken conductors
Malfunction of one or more poles of a circuit breaker or a disconnector
NS2PTOC (46I2) can also be used as a backup protection, that is, to protect the generator
in case line protections or circuit breakers fail to clear unbalanced system faults.
Range or value
15 ms typically
(2-150)% of VBase
10 ms typically at 2 to 0 x V
set
15 ms typically
(2-200)% of VBase
(0.000-60.000) s
IEC 61850
identification
NS2PTOC
Section 8
Current protection
Accuracy
-
± 0.5% of V
at V<V
n
± 0.5% of V at V>V
-
-
± 0.5% of V
at V<V
n
± 0.5% of V at V>V
± 0.5% ± 25 ms
IEC 60617
ANSI/IEEE C37.2
identification
device number
2I2>
46I2
n
n
n
n
265