ABB Relion Technical Manual page 170

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 7
Impedance protection
164
IEC10000176 V2 EN
Figure 68:
Mho, offset mho characteristic for Zone 1 with setting parameters Z1Fwd,
Z1Rev and ImpedanceAng
The three impedance zones can be time delayed individually by setting the parameter tZx
(where x is 1-3 depending on selected zone). For instantaneous operation set the parameter
tZx to 0.00 s for the particular zone. To enable the zone, the operation mode for the zone, x
(where x is 1-3 depending on selected zone), has to be set to Enable-Zone.
The function are blocked in the following ways:
Activating of input BLOCK blocks the whole function.
Activating of the input BLKZ (fuse failure) blocks all output signals.
The activation of input signal BLKZ can be made by external or internal fuse failure
function.
X
ImpedanceAng
IEC10000176-2-en.vsd
1MRK 502 048-UUS A
R
Technical manual