Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 14
Monitoring
14.15.5
Table 422:
SSIMG (63) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PressAlmLimit
0.00 - 25.00
PressLOLimit
0.00 - 25.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tPressureAlarm
0.000 - 60.000
tPressureLO
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetPressAlm
0.000 - 60.000
tResetPressLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
14.15.6
598
Table 421:
SSIMG (63) Output signals
Name
Type
PRESSURE
REAL
PRES_ALM
BOOLEAN
PRES_LO
BOOLEAN
TEMP
REAL
TEMP_ALM
BOOLEAN
TEMP_LO
BOOLEAN

Settings

Unit
Step
-
-
-
0.01
-
0.01
-
0.01
-
0.01
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
Operation principle
Insulation gas monitoring function SSIMG (63) is used to monitor gas pressure in the
circuit breaker. Two binary output signals are used from the circuit breaker to initiate
alarm signals, pressure below alarm level and pressure below lockout level. If the input
signal PRES_ALM is high, which indicate that the gas pressure in the circuit breaker is
below alarm level, the function initiates output signal PRES_ALM, pressure below alarm
level, after a set time delay and indicate that maintenance of the circuit breaker is required.
Similarly, if the input signal PRES_LO is high, which indicate gas pressure in the circuit
breaker is below lockout level, the function initiates output signal PRES_LO, after a time
Description
Pressure service value
Pressure below alarm level
Pressure below lockout level
Temperature of the insulation medium
Temperature above alarm level
Temperature above lockout level
Default
Description
Disabled
Disable/Enable Operation
5.00
Alarm setting for pressure
3.00
Pressure lockout setting
30.00
Temperature alarm level setting of the medium
30.00
Temperature lockout level of the medium
0.000
Time delay for pressure alarm
0.000
Time delay for pressure lockout indication
0.000
Time delay for temperature alarm
0.000
Time delay for temperture lockout
0.000
Reset time delay for pressure alarm
0.000
Reset time delay for pressure lockout
0.000
Reset time delay for temperture lockout
0.000
Reset time delay for temperture alarm
1MRK 502 048-UUS A
Technical manual