Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 5
Local Human-Machine-Interface LHMI
5.3.4
Table 18:
LEDGEN Non group settings (basic)
Name
Values (Range)
Operation
Off
On
tRestart
0.0 - 100.0
tMax
0.0 - 100.0
Table 19:
GRP1_LED1 Non group settings (basic)
Name
Values (Range)
SequenceType
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
LabelOff
0 - 18
LabelRed
0 - 18
LabelYellow
0 - 18
LabelGreen
0 - 18
66
Table 16:
GRP1_LED1 Input signals
Name
Type
HM1L01R
BOOLEAN
HM1L01Y
BOOLEAN
HM1L01G
BOOLEAN
Table 17:
LEDGEN Output signals
Name
Type
NEWIND
BOOLEAN
ACK
BOOLEAN

Settings

Unit
Step
-
-
s
0.1
s
0.1
Unit
Step
-
-
-
1
-
1
-
1
-
1
Default
Description
0
Red indication of LED1, local HMI alarm group 1
0
Yellow indication of LED1, local HMI alarm group 1
0
Green indication of LED1, local HMI alarm group 1
Description
New indication signal if any LED indication input is set
A pulse is provided when the LEDs are acknowledged
Default
Description
Off
Operation Off/On
0.0
Defines the disturbance length
0.0
Maximum time for the definition of a
disturbance
Default
Description
Follow-S
Sequence type for LED 1, local HMI alarm
group 1
G1L01_OFF
Label string shown when LED 1, alarm group 1
is off
G1L01_RED
Label string shown when LED 1, alarm group 1
is red
G1L01_YELLOW
Label string shown when LED 1, alarm group 1
is yellow
G1L01_GREEN
Label string shown when LED 1, alarm group 1
is green
1MRK 502 048-UUS A
Technical manual