Section 13
Logic
13.6.5
13.6.6
13.6.7
494
Table 334:
B16IFCVI Output signals
Name
Type
OUT
INTEGER

Settings

The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)
Monitored data
Table 335:
B16IFCVI Monitored data
Name
Type
OUT
INTEGER
Operation principle
The Boolean 16 to integer conversion with logic node representation function
(B16IFCVI) will transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, to
an integer. Each INx represents a value according to the table below from 0 to 32768. This
follows the general formula: INx = 2
activated INx will be available on the output OUT as a sum of the integer values of all the
inputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16) are
activated, that is = Boolean 1, it corresponds to that integer 65535 is available on the
output OUT. The B16IFCVI function is designed for receiving the integer input from a
station computer - for example, over IEC 61850. If the BLOCK input is activated, it will
freeze the logical outputs at the last value.
Values of each of the different OUTx from function block B16IFCVI for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT
on the function block B16IFCVI.
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
Table continues on next page
Description
Output value
Values (Range)
Unit
-
-
x-1
where 1≤x≤16. The sum of all the values on the
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
1MRK 502 048-UUS A
Description
Output value
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
Technical manual