Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 12
Control
12.4.5
Table 265:
SLGGIO Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
NrPos
2 - 32
OutType
Pulsed
Steady
tPulse
0.000 - 60.000
tDelay
0.000 - 60000.000
StopAtExtremes
Disabled
Enabled
12.4.6
12.4.7
450

Settings

Unit
Step
-
-
-
1
-
-
s
0.001
s
0.010
-
-
Monitored data
Table 266:
SLGGIO Monitored data
Name
Type
SWPOSN
INTEGER
Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGGIO)
function has two operating inputs – UP and DOWN. When a signal is received on the UP
input, the block will activate the output next to the present activated output, in ascending
order (if the present activated output is 3 – for example and one operates the UP input, then
the output 4 will be activated). When a signal is received on the DOWN input, the block
will activate the output next to the present activated output, in descending order (if the
present activated output is 3 – for example and one operates the DOWN input, then the
output 2 will be activated). Depending on the output settings the output signals can be
steady or pulsed. In case of steady signals, in case of UP or DOWN operation, the
previously active output will be deactivated. Also, depending on the settings one can have
a time delay between the UP or DOWN activation signal positive front and the output
activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the desired
position directly (without activating the intermediate positions), either locally or
remotely, using a "select before execute" dialog. One can block the function operation, by
activating the BLOCK input. In this case, the present position will be kept and further
operation will be blocked. The operator place (local or remote) is specified through the
Default
Description
Disabled
Operation Enable/Disable
32
Number of positions in the switch
Steady
Output type, steady or pulse
0.200
Operate pulse duration
0.000
Output time delay
Disabled
Stop when min or max position is reached
Values (Range)
Unit
-
-
1MRK 502 048-UUS A
Description
Switch position as integer
value
Technical manual