Monitored Data - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 7
Impedance protection
Table 74:
OOSPPAM (78) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
ForwardR
0.00 - 1000.00
ForwardX
0.00 - 1000.00
InvertCTCurr
No
Yes
ReverseR
0.00 - 1000.00
ReverseX
0.00 - 1000.00
Table 75:
OOSPPAM (78) Non group settings (advanced)
Name
Values (Range)
StartAngle
90.0 - 130.0
TripAngle
15.0 - 90.0
7.4.6
176
Unit
Step
-
1
% Zb
0.01
% Zb
0.01
-
-
% Zb
0.01
% Zb
0.01
Unit
Step
Deg
0.1
Deg
0.1

Monitored data

Table 76:
OOSPPAM (78) Monitored data
Name
Type
VOLTAGE
REAL
CURRENT
REAL
R
REAL
X
REAL
ROTORANG
REAL
UCOSPHI
REAL
Default
Description
1
Selection of one of the Global Base Value
Groups
1.00
Real part of total forward impedance for Z2, in
% of VBase/(sqrt(3)*IBase)
10.00
Imag. part of total forward impedance for Z2, in
% of VBase/(sqrt(3)*IBase)
No
Invert current direction
1.00
Real part of source impedance behind relay, in
% of VBase/(sqrt(3)*IBase)
10.00
Imag. part of source impedance behind relay,
in % of VBase/(sqrt(3)*IBase)
Default
Description
110.0
Angle between two rotors to get the pick up
signal, in deg
60.0
Maximum rotor angle to allow trip signals, in
deg
Values (Range)
Unit
-
kV
-
A
-
%
-
%
-
deg
-
kV
1MRK 502 048-UUS A
Description
Magnitude of the measured
positive-sequence voltage, in
V
Magnitude of the measured
positive-sequence current, in
A
Real part of measured
positive-sequence impedance
% of VBase/(sqrt(3)*IBase)
Imaginary part of measured
positive-seq impedance % of
VBase/(sqrt(3)*IBase)
Rotor angle as estimated by
the out-of-step function
Estimated Ucos(Phi) voltage
during pole slip, in V
Technical manual