Binary Inputs - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
19.4
19.5
19.6
Technical manual

Binary inputs

Table 555:
Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption/input
Threshold voltage
Signal outputs
Table 556:
Signal output and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
Power outputs
Table 557:
Power output relays without TCM function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
Value
Maximum input voltage 300 V DC
24...250 V DC
1.6...1.8 mA
<0.38 W
15...221 V DC (parametrizable in the range in steps of
1% of the rated voltage)
Value
250 V AC/DC
5 A
10 A
30 A
≤0.5 A/≤0.1 A/≤0.04 A
Value
250 V AC/DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
Section 19
Technical data