Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
15.2.5
Table 456:
ETPMMTR Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
StartAcc
Disabled
Enabled
tEnergy
1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
tEnergyOnPls
0.000 - 60.000
tEnergyOffPls
0.000 - 60.000
EAFAccPlsQty
0.001 - 10000.000
EARAccPlsQty
0.001 - 10000.000
ERFAccPlsQty
0.001 - 10000.000
ERRAccPlsQty
0.001 - 10000.000
Table 457:
ETPMMTR Non group settings (advanced)
Name
Values (Range)
EALim
0.001 -
10000000000.000
ERLim
0.001 -
10000000000.000
EnZeroClamp
Disabled
Enabled
LevZeroClampP
0.001 - 10000.000
LevZeroClampQ
0.001 - 10000.000
DirEnergyAct
Forward
Reverse
DirEnergyReac
Forward
Reverse
EAFPrestVal
0.000 - 10000.000
EARPrestVal
0.000 - 10000.000
ERFPresetVal
0.000 - 10000.000
ERRPresetVal
0.000 - 10000.000
Technical manual

Settings

Unit
Step
-
-
-
-
-
-
s
0.001
s
0.001
MWh
0.001
MWh
0.001
MVArh
0.001
MVArh
0.001
Unit
Step
MWh
0.001
MVArh
0.001
-
-
MW
0.001
MVAr
0.001
-
-
-
-
MWh
0.001
MWh
0.001
MVArh
0.001
MVArh
0.001
Default
Description
Disabled
Operation Enable/Disable
Disabled
Activate the accumulation of energy values
1 Minute
Time interval for energy calculation
1.000
Energy accumulated pulse ON time
0.500
Energy accumulated pulse OFF time
100.000
Pulse quantity for active forward accumulated
energy value
100.000
Pulse quantity for active reverse accumulated
energy value
100.000
Pulse quantity for reactive forward
accumulated energy value
100.000
Pulse quantity for reactive reverse
accumulated energy value
Default
Description
1000000.000
Active energy limit
1000.000
Reactive energy limit
Enabled
Enable of zero point clamping detection
function
10.000
Zero point clamping level at active Power
10.000
Zero point clamping level at reactive Power
Forward
Direction of active energy flow Forward/
Reverse
Forward
Direction of reactive energy flow Forward/
Reverse
0.000
Preset Initial value for forward active energy
0.000
Preset Initial value for reverse active energy
0.000
Preset Initial value for forward reactive energy
0.000
Preset Initial value for reverse reactive energy
Section 15
Metering
635

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi