ABB 650 series Engineering Manual
Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

®
Relion
Protection and Control
650 series
Engineering Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB 650 series

  • Page 1 ® Relion Protection and Control 650 series Engineering Manual...
  • Page 3 Document ID: 1MRK 511 261-UEN Issued: June 2012 Revision: - Product version: 1.2 © Copyright 2012 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Product documentation set............6 Document revision history.............7 Related documents................7 Symbols and conventions..............8 Symbols..................8 Document conventions..............8 Functions included in 650 series IEDs..........9 Section 2 Engineering tool set............15 Introduction..................15 IED engineering process..............16 Section 3 Engineering process............19 Workflow...................19 Section 4 Setting up a project............23 PCM600 operates on projects............23...
  • Page 8 RS485 serial interface on COM05 module......101 Selecting to communicate IEC60870-5-103 data via optical serial interface on COM05 module......102 Section 9 DNP3 communication engineering.......103 Signal configuration user information..........103 Adding setting groups..............104 Configuring DNP3 protocol signals..........106 Setting DNP3 signal parameters............109 650 series Engineering Manual...
  • Page 9 Table of contents Configuring DNP3 class............110 Selecting to communicate DNP3 data via RS485 serial interface on COM05 module............111 RS485 specific parameters..........111 Selecting to communicate DNP3 data via optical serial interface on COM05 module............111 Section 10 Glossary...............113 650 series Engineering Manual...
  • Page 11: Section 1 Introduction

    The system engineer must have a thorough knowledge of protection and/or control systems, protection and/or control equipment, protection and/or control functions and the configured functional logics in the IEDs. The installation and commissioning personnel must have a basic knowledge of handling electronic equipment. 650 series Engineering Manual...
  • Page 12: Product Documentation

    The manual can also be used by system engineers and maintenance personnel for assistance during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as 650 series Engineering Manual...
  • Page 13: Document Revision History

    Document revision history Document revision/date History -/June 2012 First release 1.3.3 Related documents 650 series manuals Identity number Communication protocol manual, DNP3 1MRK 511 257-UEN Communication protocol manual, IEC 61850–8–1 1MRK 511 258-UEN Communication protocol manual, IEC 60870-5-103 1MRK 511 259-UEN...
  • Page 14: Symbols And Conventions

    Section 1 1MRK 511 261-UEN - Introduction 650 series manuals Identity number Operation manual 1MRK 500 095-UEN Installation manual 1MRK 514 015-UEN Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 15: Functions Included In 650 Series Ieds

    1.4.3 Functions included in 650 series IEDs Table 1: Main protection functions IEC 61850 / Function block...
  • Page 16 SAPTOF Overfrequency function SAPFRC Rate-of-change frequency protection Table 3: Control and monitoring functions IEC 61850 / Function ANSI Function description block name Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser Table continues on next page 650 series Engineering Manual...
  • Page 17 Function commands user defined for IEC60870-5-103 I103GENCMD Function commands generic for IEC60870-5-103 I103POSCMD IED commands with position and select for IEC60870-5-103 Secondary system supervision CCSRDIF Current circuit supervision SDDRFUF Fuse failure supervision Table continues on next page 650 series Engineering Manual...
  • Page 18 Function block for service value presentation of secondary analog inputs 600AIM CNTGGIO Event counter DRPRDRE Disturbance report AxRADR Analog input signals BxRBDR Binary input signals SPGGIO IEC61850 generic communication I/O functions SP16GGIO IEC61850 generic communication I/O functions 16 inputs Table continues on next page 650 series Engineering Manual...
  • Page 19 Horizontal communication via GOOSE for interlocking GOOSEBINRCV GOOSE binary receive ETHFRNT Ethernet configuration of front port, LAN1 port and gateway ETHLAN1 GATEWAY GOOSEDPRCV GOOSE function block to receive a double point value Table continues on next page 650 series Engineering Manual...
  • Page 20 Summation block 3 phase GBASVAL Global base values for settings DOSFRNT Denial of service, frame rate control for front port DOSLAN1 Denial of service, frame rate control for LAN1 port DOSSCKT Denial of service, socket flow control 650 series Engineering Manual...
  • Page 21: Section 2 Engineering Tool Set

    IEDs. Product type and version specific engineering data needed by PCM600 for protection, control and communication engineering of a particular bay IED is given in an IED connectivity package. 650 series Engineering Manual...
  • Page 22: Ied Engineering Process

    IEDs and station IEDs. A PC with PCM600 can be connected to any 650 series IED within a station using the Ethernet connection. The Ethernet connection can then later also be used for service and maintenance purposes.
  • Page 23 Listing all actual existing IED internal events by using the Event Viewer tool. • Listing all actual pending process events as they are stored in the IED internal disturbance report event list by using the Event Viewer tool. 650 series Engineering Manual...
  • Page 24 Conversely some parts of the engineering information can be uploaded from the IED for various purposes. The connection between the physical IED and PCM600 is established via an Ethernet link on the front or rear port on the IED. 650 series Engineering Manual...
  • Page 25: Section 3 Engineering Process

    IET600 Export SCL files from IET600. Import Import SCL files to PCM600 Make GOOSE connections Write configuration Write configuration to IED to IED WRITE WRITE IEC08000122.vsd IEC08000122 V2 EN Figure 4: IED engineering workflow 650 series Engineering Manual...
  • Page 26 • Build the plant structure according to the substation structure. For performance reasons, do not insert more than 150 IEDs of 650 series type in one PCM600 project. Larger projects can be divided into several PCM600 projects. • Insert an IED in plant structure which can be done in many ways. By...
  • Page 27 The IED will reboot at the next PCM600 to IED write operation only in case there are errors while configuring the IEC61850 protocol at the most recent attempt. 650 series Engineering Manual...
  • Page 29: Section 4 Setting Up A Project

    A Connectivity package for a specific IED type and version is divided in two parts. The IED connectivity package base module is common for all 650 series IEDs. The IED specific module is separate for each type of IED.
  • Page 30: Setting Technical Key

    PCM600 technical key to the IED. The user can also define an own technical key. The error message displayed due to mismatch between PCM600 and IED technical key is shown in Figure IEC09000378-1-en.vsd IEC09000378 V1 EN Figure 5: Error message due to mismatch between PCM600 and IED technical key 650 series Engineering Manual...
  • Page 31 PCM600: Set technical key menu at IED level A dialog window opens to inform about the technical key concept. Click OK in the dialog window. The technical key is read from the IED and the technical key editor window opens, see Figure 650 series Engineering Manual...
  • Page 32: Setting Up Communication Between Pcm600 And The Ied

    To connect PCM600 to the IED, two basic variants must be considered. • Direct point-to-point link between PCM600 and the IED front port. • Indirect link via a station LAN or from remote via a network. 650 series Engineering Manual...
  • Page 33 Tx with Rx on the other side and vice versa. These cables are known as cross over cables. The maximum length should be about 2 m. The connector type is RJ-45. 650 series Engineering Manual...
  • Page 34 IEDs DHCP server for the front port assigns an IP address for the PC. The PC must be configured to obtain its IP address automatically as described in the following procedure. Select Network Connections in the PC. 650 series Engineering Manual...
  • Page 35 Select: Network connections Select Properties in the status window. IEC09000356-1-en.vsd IEC09000356 V1 EN Figure 10: Right-click Local Area Connection and select Properties Select the TCP/IP protocol from the list of configured components using this connection and click Properties. 650 series Engineering Manual...
  • Page 36 IP address is not set to be obtained automatically by the IED, see Figure 13. The IP address must be different from the IP address chosen for the IED. 650 series Engineering Manual...
  • Page 37: Project Managing In Pcm600

    It is possible to: • Open existing projects • Import projects • Create new projects • Export projects • Delete projects • Rename projects • Copy and paste projects • Migrate projects from one product version to another 650 series Engineering Manual...
  • Page 38: Building A Plant Structure

    PCM600 sets up a new project that will be listed under Projects on my computer. Building a plant structure The plant structure is used to identify each IED in its location within the substation organization. It is a geographical image of the substation and the bays within the 650 series Engineering Manual...
  • Page 39 Rename the level after insertion, using the Rename possibility or the Object Properties. Figure 15 shows the start of a project with two IEDs placed but still not renamed. The plant structure corresponds to the complete grid including the needed IEDs. Procedure to build a plant structure: 650 series Engineering Manual...
  • Page 40: Iec 61850 Naming Conventions To Identify An Ied

    SCL technical key for the station level, voltage level, bay level and IED level using the Object properties window as shown in Figure 650 series Engineering Manual...
  • Page 41: Inserting An Ied

    PCM600: IEC 61850 signal designation concept Inserting an IED The context menu or the Object Types view shows the available 650 series IEDs possible to insert, on the bay level in the plant structure, according to the installed connectivity package.
  • Page 42 Right-click the Bay and select New and Sub-Transmission IEDs. Select the IED type to insert. It is also possible to drag an IED from the Object Types window to the Bay level. Select the Online Configuration mode, see Figure 650 series Engineering Manual...
  • Page 43 PCM600: Configuration mode selection wizard Select the IED Communication protocol, see Figure IEC09000661-1-en.vsd IEC09000661 V1 EN Figure 19: PCM600: Communication protocol selection wizard Select the port and insert the IP address of the physical IED to configure, see Figure 650 series Engineering Manual...
  • Page 44 The user can not scan data from the IED or proceed further if the IED is not online or if the IP address is not correct. Click the Scan option to scan/read the IED Type and IED Version for the IED that is online, see Figure 650 series Engineering Manual...
  • Page 45 Click next to open the Housing Selection Page and select the housing and display type of the IED, see Figure 22 IEC09000682-1-en.vsd IEC09000682 V1 EN Figure 22: PCM600: IED housing and display type detection The Setup Complete Page dialog shows the summary of the 650 series Engineering Manual...
  • Page 46 IED has to be inserted again. When the online configuration is completed, it is advised to read the configuration from the IED to ensure that the IED object in PCM600 has the same configuration data as the physical IED. 650 series Engineering Manual...
  • Page 47 The order specific file is delivered in a order confirmation E-mail. If no order specific file is available then select the No Order Specific File option, see Figure IEC09000665 V4 EN Figure 24: PCM600: IED Version selection 650 series Engineering Manual...
  • Page 48 In 650 series version 1.2.1 some hardware selections are possible to make even if they are not possible to order. It will not be possible to download an invalid hardware configuration to the IED.
  • Page 49 A template IED can only be inserted when the bay is selected in the plant structure. Procedure to insert a template IED Right-click the Bay in the plant structure. Select New and Create from Template ... to open the Create New Object from Template window, see Figure 650 series Engineering Manual...
  • Page 50 Figure 28: PCM600: IED Template Properties Click Delete Template to delete the template, click Import Template to import a template from the selection window or click Create to insert the selected IED to the bay, see Figure 650 series Engineering Manual...
  • Page 51 IED object in PCM600. The configured IEDs in 650 series is bound to a specific hardware configuration. Configured IEDs in 650 series are available on the Connpack DVD as .pcmi files under the file named User documentation.
  • Page 52: Setting Ied Ip Address In The Project

    Via the first window of the wizard when including a new IED in a project, see Figure IEC09000662-1-en.vsd IEC09000662 V1 EN Figure 30: Alternative 1: IP address via first Wizard window • Via the IP address property of the IED in the Object Properties window, see Figure 650 series Engineering Manual...
  • Page 53 Select the IED to enter the IP address. Open the Object Properties window. Place the cursor in the IP address row and enter the IP address. The used alternative depends on the time at which the IP address is available. 650 series Engineering Manual...
  • Page 55: Section 5 Protection And Control Engineering

    Features to program an application configuration: • Insert function blocks, make connections and create variables. • Include the hardware IO channels directly in the application configuration. • Set function blocks and signal visibility to SMT and PST. 650 series Engineering Manual...
  • Page 56: Function Blocks

    Set IEC or/and ANSI naming style. • Lock function blocks. • Set visibility for execution order, cycle time and instance number. • Manage signals, for example hide, show and rearrange. • Invert Boolean inputs and Boolean outputs. 650 series Engineering Manual...
  • Page 57 Inverted output Hardware, binary output channel 10 Hardware, analog input channel 11 User defined signal name 12 Hardware, binary input channel 13 Execution order 14 Cycle time 15 Instance number 16 Inverted input 17 Signal description note 650 series Engineering Manual...
  • Page 58: Signals And Signal Management

    The cycle time may be predefined to one value. The instance number is a counter for the total possible number of function blocks of that type used within an application configuration. 650 series Engineering Manual...
  • Page 59 The Cycle Time can be selected to 5, 20 or 100 ms. Depending on function block type and the 650 series product only one, two or all three possibilities may be available.
  • Page 60 Figure 35: Cycle time and execution order A function block type can be defined to be a member of one or several cycle times. A function block instance can be set only to one cycle time. 650 series Engineering Manual...
  • Page 61: Configuration Parameters

    Link two signals by using variables. It is possible to search and replace variable names in ACT. Connection validation A connection is only useful and possible between two signals of the same data type, see Figure 650 series Engineering Manual...
  • Page 62: Hardware Channels

    A hardware input channel can be used as often as it is needed. A hardware binary output channel is taken from the list of available channels when a new channel is requested. That prevents for using a hardware binary output channel twice. As an example, see Figure 650 series Engineering Manual...
  • Page 63: Validation

    Validation is made when creating the application configuration, for example: • A connection between two input signals or two output signals is not possible. • A connection between two different data types is not possible, for example a binary output to an analog input. 650 series Engineering Manual...
  • Page 64 ACT: Validation on demand Validation when writing to the IED When writing the application configuration to the IED an automatic validation is performed. The validation is the same as the manually demanded validation. Errors will abort the writing. 650 series Engineering Manual...
  • Page 65: Setting Configuration And Setting Parameters In Pst

    Nearly all settings used by the IED for the protection application functions are organized in a group of settings. Up to four setting groups can be configured with different values. The IED supports the selection of a setting group at runtime. 650 series Engineering Manual...
  • Page 66: Connecting Signals In Smt

    IO signals and function blocks. • for the GOOSE engineering. SMAI GOOSE FBs for IEC 61850 binary and analog GOOSE Inputs data, interlocking communication and voltage control IEC08000173_2_en.vsd IEC08000173 V2 EN Figure 40: SMT: Operation principles 650 series Engineering Manual...
  • Page 67 IEC08000150-2-en.vsd IEC08000150 V2 EN Figure 41: SMT Connection between binary input channels to binary input signals Depending on the IED capability, SMT has a separate sheet for each possible combination. The possible sheets are: 650 series Engineering Manual...
  • Page 68 Section 5 1MRK 511 261-UEN - Protection and control engineering • Binary Inputs • Binary Outputs • Analog Inputs • GOOSE Receive 650 series Engineering Manual...
  • Page 69: Section 6 Local Hmi Engineering

    Set function keys and LEDs SAVE GDE / ACT Create the single line diagram SAVE IEC09000622_1_en.vsd IEC09000622 V1 EN Figure 42: LHMI: Engineering process flowchart • Application Configuration tool with possible assistance of Signal Matrix tool 650 series Engineering Manual...
  • Page 70 15 LEDs and their belonging text elements on the LCD [A]. They are operated by the keys [a] and [b]. The other group is the five function keys with their IEDs and the corresponding text elements on the LCD [B]. 650 series Engineering Manual...
  • Page 71 • The LED signal of the key is independent of the key function and must be programed to process demands. • The function block handles the operators command when the key is pressed as output signal. 650 series Engineering Manual...
  • Page 72 Figure • General definitions • Each LED can illuminate in one of three colors: RED, YELLOW, GREEN. • Only one color is illuminated at a time. • The priority for illumination and the color is linked. 650 series Engineering Manual...
  • Page 73 This mode is used for all LEDs that are used to indicate a disturbance. The LEDs will stay in the last state after the disturbance run time until they are reset after a defined time. • The timers are set in Parameter Setting tool in the function block LEDGEN. 650 series Engineering Manual...
  • Page 74: Led Operation Modes

    Six operation modes are listed in the drop down menu in Parameter Setting tool. • Follow-S • Follow-F • LatchedAck-F-S • LatchedAck-S-F • LatchedColl-S • LatchedReset-S LED operation mode Follow-S Illumination => = Steady = Flash IEC08000395.vsd IEC08000395 V1 EN Figure 46: LHMI: LED operation mode Follow-S 650 series Engineering Manual...
  • Page 75 Two possibilities for the operator to acknowledge: • The signal is already gone when acknowledged, the LED turns OFF (at least for this color). • The signal is still ON, the LED stays illuminated and changes to steady state. 650 series Engineering Manual...
  • Page 76 The higher priority color (signal) will illuminate in flash mode. Figure 49 Figure 50 for these two principles. Illumination => = Steady = Flash IEC08000399.vsd IEC08000399 V1 EN Figure 50: LHMI LED operation mode LatchedAck-F-S Prio / 2 650 series Engineering Manual...
  • Page 77 The thin dashed lines in Figure 51 shows the internal state of the LED following the signal and reset, when no higher prior signal is given. The LED illuminates always in steady mode. 650 series Engineering Manual...
  • Page 78 A disturbance runs for a maximum of some seconds, while tReset can be in the range of 60 to 90 seconds. The timer tReset and tMax are configured in Parameter Setting tool as part of the function block LEDGEN 650 series Engineering Manual...
  • Page 79: Single-Line Diagram Engineering

    LHMI. 6.2.1 Concept description to present and generate diagrams in graphical display editor Additional concept information to use GDE, see Figure • Different GDE windows • HMI display raster layouts • Drawing lines (doing a Link) 650 series Engineering Manual...
  • Page 80 Display window and sequence order It is important to link correctly between the HMI display page and the corresponding bay that is presented as a single line diagram on this HMI page. Rules to handle HMI pages: 650 series Engineering Manual...
  • Page 81 ACT are of type xxxGGIO. • Select Dynamic Text and Indication to present the text for the actual value of the function block, see Figure • Click Select Button to select the value. 650 series Engineering Manual...
  • Page 82 Unit and scaling of the signal can only be changed via the property window. Select and toggle Show Texts using the IED Fonts to get a view how it will look like later on the real HMI display. 650 series Engineering Manual...
  • Page 83 Center once again the mouse pointer and click to drop the line. Draw all line elements that are necessary. Click Select in the menu bar to finish the line drawing. Line draw icon start point end point en05000598.vsd IEC05000598 V1 EN Figure 56: GDE: Drawing a line 650 series Engineering Manual...
  • Page 84: Supported Single-Line Diagram Symbols

    Coil Others Transformer 2 winding Power transformers Transformer 3 winding Power transformers Autotransformer Power transformers Isolator, 00 = middle position Switchgear Isolator, 01 = Open Switchgear Isolator, 10 = Closed Switchgear Table continues on next page 650 series Engineering Manual...
  • Page 85 Switchgear Undefined Isolator motor operated, 00 = Switchgear Middle position Isolator motor operated, 01 = Switchgear Open Isolator motor operated, 10 = Switchgear Closed Isolator motor operated, 11 = Switchgear Undefined Table continues on next page 650 series Engineering Manual...
  • Page 86 Breaker2 indication only, 11 = Switchgear Undefined Static text Texts Dynamic text Texts Select button, 00 = Middle Texts position Select button, 01 = Open Texts Select button, 10 = Closed Texts Table continues on next page 650 series Engineering Manual...
  • Page 87: Bay Configuration Engineering

    10. Validate that all links are done. 11. Save the complete picture. 12. Repeat the steps for all pages when more than one is needed. 13. Write the display configuration to IED from the GDE tool. 650 series Engineering Manual...
  • Page 88 • All configured function blocks with measurements (of type MMXU) for the measurements. • VSGGIO for one bit indications for the dynamic text symbols. • SLGGGIO for 32 bit indications for the dynamic text symbols. Procedure 650 series Engineering Manual...
  • Page 89 The number of order in the selection window of the process objects corresponds to the number given in the PST tree and to the application function block in ACT. Only those apparatus and measurements are shown that are configured in the application configuration program. 650 series Engineering Manual...
  • Page 90 As the function delivers angles in radians, a scale factor of 180/pi = 57,3 shall be used to display the angle in degrees IEC10000174.vsd IEC10000174 V1 EN Figure 60: GDE: Object properties window for unit change 650 series Engineering Manual...
  • Page 91: Events And Indications

    To get IED events to the LHMI event list and indications for Ready, Start and Trip indication LEDs, disturbance report needs to be engineered. Detailed information about disturbance report subfunctions is found in the technical manual. 650 series Engineering Manual...
  • Page 93: Section 7 Iec 61850 Communication Engineering

    ACT will be automatically created. This means that the user do not need to handle any instance information for the functions regarding IEC 61850. 7.1.2 IEC 61850 interface in IED Figure 61 for a principle view of the IEC 61850 logical node concept in the IED. 650 series Engineering Manual...
  • Page 94: Goose Data Exchange

    Ethernet. Whoever needs the information detects the telegram by its source address and will read the telegram and deals with it. The telegrams are multicast sent and not acknowledged by the receiver. 650 series Engineering Manual...
  • Page 95: Station Configuration Description File Types

    These files have a different definition, which is explained in IEC 61850–6. Three of these file types are used in the engineering process for an IED. • ICD = IED Capability Description The IED name in an exported .icd file is always named TEMPLATE. 650 series Engineering Manual...
  • Page 96: Iec 61850 Engineering Procedure

    • An IED is already extended by default data sets. They are predefined by ABB. Changes or additional data sets, for example, have to be done with the IET600 station configuration tool. •...
  • Page 97: Exporting Scl Files From Pcm600

    The used interface addresses have to be set according to protocol and project definitions. The station communication port has to be activated in the IED, that is to set the IEC61850-8-1Operation setting to On. 7.3.1 Exporting SCD files Procedure to export the SCD file from PCM600: 650 series Engineering Manual...
  • Page 98: Exporting Icd Or Cid Files

    Select the type of file to export from the Save as type drop down list. • Configured IED Description (*.cid) for the IEC 61850 structure as needed for the IED at runtime. • IED Capability Description (*.icd) for the IEC 61850 structure, see Figure 650 series Engineering Manual...
  • Page 99: Engineering Of Vertical And Horizontal Communication In Iet600

    Import the SCD file exported from PCM600. All data sets, report control blocks and GOOSE control blocks must be located at LD0/LLN0. Due to IED capability, there are limitations regarding the maximum number of data sets, 650 series Engineering Manual...
  • Page 100 Connect the report control blocks to vertical IED clients. The report control blocks are connected to the vertical clients in the SCD file for a 650 series pre- configured IED. Check each IED client and configure them to the subnetwork before connecting report control blocks to the clients.
  • Page 101: Importing Scl Files To Pcm600

    SCD file does not match the original configuration in PCM600. 4.3. Click Replace unknown ... can be used when it is known, that the file includes additional IEDs that are needed. The IED of type “Generic IEC 650 series Engineering Manual...
  • Page 102 GOOSE receiving function blocks in the application configuration to enable GOOSE communication. Write the configuration to the IED, see Figure Note that the engineered data is written to the IED when executing a common Write to IED operation. 650 series Engineering Manual...
  • Page 103: Importing Icd Or Cid Files

    Select the file type of IEC 61850 to import from the Files of type drop down list (ICD or CID) The SCL Import Option menu opens, which queries how the file should be handled during import, see Figure 650 series Engineering Manual...
  • Page 104: Writing Communication Configuration To Ied

    Configuration tool configuration is changed, but no changes are done for the instantiation or deletion of functions that represent a logical node. When a changed configuration is written to the IED, the user is asked to update the communication configuration. 650 series Engineering Manual...
  • Page 105 If no changes have been done in the communication configuration part, click No in the Update Communication window. IEC09000729-1-en.vsd IEC09000729 V1 EN Figure 71: Update the communication configuration in the IED with the configuration made in PCM600 650 series Engineering Manual...
  • Page 107: Section 8 Iec 60870-5-103 Communication Engineering

    Parameter Setting tool. See the Communication protocol manual for IEC 60870-5-103 for more information about the IEC 60870-5-103 implementation in 650 series. The COM05 module is equipped with an optical serial and RS485 serial communication interface. IEC60870-5-103 can be communicated from either of these serial interfaces.
  • Page 108: Selecting To Communicate Iec60870-5-103 Data Via Optical Serial Interface On Com05 Module

    To enable the IEC60870-5-103 protocol on the RS485 port, select IEC103 for setting Operation. Navigate to the OPTICAL103 function block, found in MainMenu/ IEDConfiguration/Communication/I103/OPTICAL103:1, to set IEC60870-5-103 communications port properties, such as baud-rate or master time domain. 650 series Engineering Manual...
  • Page 109: Section 9 Dnp3 Communication Engineering

    DNP3 protocol presentation. This can be done when the Configuration Table View is selected. Finally, the signal configuration to the different DNP3 channels can be listed in a report on demand and per signal type. 650 series Engineering Manual...
  • Page 110: Adding Setting Groups

    To make it easier to recognize the signals for the active setting group, the user-defined names are used. Open the Communication Management Tool (CMT). Set the Signal Type to Binary Input Object and choose the connection of the master for which the values should be presented. 650 series Engineering Manual...
  • Page 111 Communication Management tool Select the signals and move them into the DNP signal list of the master. DNP point zero and one of the Binary Input Objects are used for indicating the active setting group in this case. 650 series Engineering Manual...
  • Page 112: Configuring Dnp3 Protocol Signals

    Save the actual project configuration in PCM600 to make all signals visible for CMT. Direct configured hardware channels in the application configuration (see Figure 75) appear in CMT (see Figure 76). Do not configure these hardware channels to be sent by DNP3, as they are not event-handled. 650 series Engineering Manual...
  • Page 113 DNP3. • The right window shows tabs for possible communication channels. • The left window has a drop down menu for signal selection and buttons for signal movement, see Figure 650 series Engineering Manual...
  • Page 114 Repeat to move signals for all signal types and save the selection. Content changes in the DNP3 container are marked with a star at the end of the name, see Figure 79. The star indicates that changes in the container have to be saved before leaving CMT. 650 series Engineering Manual...
  • Page 115: Setting Dnp3 Signal Parameters

    Set Index ... from the context menu to move one or a set of signals to another array, see Figure IEC08000336.vsd IEC08000336 V1 EN Figure 80: CMT: Context menu in DNP3 window The selection window shows the number of signals selected, see Figure 650 series Engineering Manual...
  • Page 116: Configuring Dnp3 Class

    In the master station the classes can be polled in sequences according to the demands in the project. Unsolicited reporting is possible as well. Modify the organization of the classes for each signal individually. Procedure 650 series Engineering Manual...
  • Page 117: Selecting To Communicate Dnp3 Data Via Rs485 Serial Interface On Com05 Module

    In PST, navigate to the OPTICALPROT function block located in MainMenu/ IEDConfiguration/Monitoring/OPTICALPROT:1. To enable the DNP3 protocol on optical serial port, select DNP for setting Operation. Navigate to the MSTSERIAL function block, located in MainMenu/ IEDConfiguration/Communication/DNP3.0/MSTSERIAL:1, and set ChToAssociate to Optical. 650 series Engineering Manual...
  • Page 119: Section 10 Glossary

    Standard format according to IEC 60255-24 Contra-directional Way of transmitting G.703 over a balanced line. Involves four twisted pairs, two of which are used for transmitting data in both directions and two for transmitting clock signals 650 series Engineering Manual...
  • Page 120 Digital signal processor Direct transfer trip scheme EHV network Extra high voltage network Electronic Industries Association Electromagnetic compatibility (Electric Motive Force) Electromagnetic interference EnFP End fault protection Enhanced performance architecture Electrostatic discharge Flow control bit; Frame count bit 650 series Engineering Manual...
  • Page 121 PCI Mezzanine Card (PMC) standard for local bus modules. References the CMC (IEEE P1386, also known as Common Mezzanine Card) standard for the mechanics and the PCI specifications from the PCI SIG (Special Interest Group) for the electrical EMF (Electromotive force). 650 series Engineering Manual...
  • Page 122 Local detection device Light-emitting diode Miniature circuit breaker Mezzanine carrier module Multifunction vehicle bus. Standardized serial bus originally developed for use in trains. National Control Centre OCO cycle Open-close-open cycle Overcurrent protection OLTC On-load tap changer Over-voltage 650 series Engineering Manual...
  • Page 123 Serial link according to EIA standard RS485 Real-time clock Remote terminal unit Substation Automation Select-before-operate Switch or push button to close Station control system SCADA Supervision, control and data acquisition System configuration tool according to standard IEC 61850 650 series Engineering Manual...
  • Page 124 See also Overreach. Coordinated Universal Time. A coordinated time scale, maintained by the Bureau International des Poids et Mesures (BIPM), which forms the basis of a coordinated dissemination of standard frequencies and time signals. UTC 650 series Engineering Manual...
  • Page 125 A digital signalling interface primarily used for telecom equipment Three times zero-sequence current. Often referred to as the residual or the earth-fault current Three times the zero sequence voltage. Often referred to as the residual voltage or the neutral point voltage 650 series Engineering Manual...
  • Page 128 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...

Table of Contents