Section 14
Monitoring
Name
Values (Range)
FunType9
0 - 255
InfNo9
0 - 255
FunType10
0 - 255
InfNo10
0 - 255
Table 391:
A1RADR Non group settings (advanced)
Name
Values (Range)
NomValue01
0.0 - 999999.9
UnderTrigOp01
Disabled
Enabled
UnderTrigLe01
0 - 200
OverTrigOp01
Disabled
Enabled
OverTrigLe01
0 - 5000
NomValue02
0.0 - 999999.9
UnderTrigOp02
Disabled
Enabled
UnderTrigLe02
0 - 200
OverTrigOp02
Disabled
Enabled
OverTrigLe02
0 - 5000
NomValue03
0.0 - 999999.9
UnderTrigOp03
Disabled
Enabled
UnderTrigLe03
0 - 200
OverTrigOp03
Disabled
Enabled
OverTrigLe03
0 - 5000
NomValue04
0.0 - 999999.9
UnderTrigOp04
Disabled
Enabled
UnderTrigLe04
0 - 200
Table continues on next page
554
Unit
Step
Default
-
1
0
-
1
0
-
1
0
-
1
0
Unit
Step
Default
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
-
0.1
0.0
-
-
Disabled
%
1
50
1MRK 502 048-UUS A
Description
Function type for analog channel 9
(IEC-60870-5-103)
Information number for analog channel 9
(IEC-60870-5-103)
Function type for analog channel 10
(IEC-60870-5-103)
Information number for analog channel10
(IEC-60870-5-103)
Description
Nominal value for analog channel 1
Use under level trigger for analog channel 1
(on) or not (off)
Under trigger level for analog channel 1 in % of
signal
Use over level trigger for analog channel 1 (on)
or not (off)
Over trigger level for analog channel 1 in % of
signal
Nominal value for analog channel 2
Use under level trigger for analog channel 2
(on) or not (off)
Under trigger level for analog channel 2 in % of
signal
Use over level trigger for analog channel 2 (on)
or not (off)
Over trigger level for analog channel 2 in % of
signal
Nominal value for analog channel 3
Use under level trigger for analog channel 3
(on) or not (off)
Under trigger level for analog channel 3 in % of
signal
Use over level trigger for analog channel 3 (on)
or not (off)
Overtrigger level for analog channel 3 in % of
signal
Nominal value for analog channel 4
Use under level trigger for analog channel 4
(on) or not (off)
Under trigger level for analog channel 4 in % of
signal
Technical manual