1MRK 502 048-UUS A
Name
Values (Range)
OpNumLO
0 - 9999
tOpenAlm
0 - 200
tCloseAlm
0 - 200
OpenTimeCorr
0 - 100
CloseTimeCorr
0 - 100
DifTimeCorr
-10 - 10
tSprngChrgAlm
0.00 - 60.00
tPressAlm
0.00 - 60.00
TPressLO
0.00 - 60.00
AccEnerInitVal
0.00 - 9999.99
CountInitVal
0 - 9999
CBRemLife
0 - 9999
InactDayAlm
0 - 9999
InactDayInit
0 - 9999
InactHourAlm
0 - 23
14.17.6
Technical manual
Unit
Step
-
1
ms
1
ms
1
ms
1
ms
1
ms
1
s
0.01
s
0.01
s
0.01
-
0.01
-
1
-
1
Day
1
Day
1
Hour
1

Monitored data

Table 431:
SSCBR Monitored data
Name
Type
CBOTRVT
REAL
CBCLTRVT
REAL
SPRCHRT
REAL
NO_OPR
INTEGER
NOOPRDAY
INTEGER
CBLIFE_A
INTEGER
CBLIFE_B
INTEGER
CBLIFE_C
INTEGER
IACC_A
REAL
IACC_B
REAL
IACC_C
REAL
Default
Description
300
Lockout limit for number of operations
40
Alarm level setting for open travel time
40
Alarm level setting for close travel time
10
Correction factor for open travel time
10
Correction factor for CB close travel time
5
Correction factor for time difference in auxiliary
and main contacts open time
1.00
Setting of alarm for spring charging time
0.10
Time delay for gas pressure alarm
0.10
Time delay for gas pressure lockout
0.00
Accumulation energy initial value
0
Operation numbers counter initialization value
5000
Initial value for the CB remaining life estimates
2000
Alarm limit value of the inactive days counter
0
Initial value of the inactive days counter
0
Alarm time of the inactive days counter in hours
Values (Range)
Unit
-
ms
-
ms
-
s
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Section 14
Monitoring
Description
Travel time of the CB during
opening operation
Travel time of the CB during
closing operation
The charging time of the CB
spring
Number of CB operation cycle
The number of days CB has
been inactive
CB Remaining life phase A
CB Remaining life phase B
CB Remaining life phase C
Accumulated currents power
(Iyt), phase A
Accumulated currents power
(Iyt), phase B
Accumulated currents power
(Iyt), phase C
605