Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 8
Current protection
8.2.5
Table 92:
EF4PTOC Group settings (basic)
Name
Values (Range)
Operation
Off
On
EnaDir
Disable
Enable
AngleRCA
-180 - 180
polMethod
Voltage
Current
Dual
UPolMin
1 - 100
IPolMin
2 - 100
RPol
0.50 - 1000.00
XPol
0.50 - 3000.00
I>Dir
1 - 100
2ndHarmStab
5 - 100
DirMode1
Off
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
IN1>
1 - 2500
t1
0.000 - 60.000
Table continues on next page
206

Settings

Unit
Step
-
-
-
-
Deg
1
-
-
%UB
1
%IB
1
ohm
0.01
ohm
0.01
%IB
1
%
1
-
-
-
-
%IB
1
s
0.001
Default
Description
Off
Operation Off / On
Enable
Enabling the Directional calculation
65
Relay characteristic angle (RCA)
Voltage
Type of polarization
1
Minimum voltage level for polarization (UN or
U2) in % of UBase
5
Minimum current level for polarization (IN or I2)
in % of IBase
5.00
Real part of source Z to be used for current
polarisation
40.00
Imaginary part of source Z to be used for
current polarisation
10
Current level (IN or I2) for direction release in %
of IBase
20
Second harmonic restrain operation in % of IN
amplitude
Non-directional
Directional mode of step 1 (off, non-directional,
forward, reverse)
ANSI Def. Time
Time delay curve type for step 1
100
Operate residual current level for step 1 in % of
IBase
0.000
Independent (definite) time delay of step 1
1MRK 502 048-UUS A
Technical manual