Operation Principle - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 14
Monitoring
Name
Values (Range)
IndicationMa15
Hide
Show
TrigLevel16
Trig on 0
Trig on 1
IndicationMa16
Hide
Show
14.4.6
568
Unit
Step
-
-
-
-
-
-

Operation principle

Disturbance report DRPRDRE is a common name for several functions to supply the
operator, analysis engineer, and so on, with sufficient information about events in the
system.
The functions included in the disturbance report are:
Sequential of events
Indications
Event recorder
Trip value recorder
Disturbance recorder
Figure 254
shows the relations between Disturbance Report, included functions and
function blocks. Sequential of events , Event recorder and Indications uses information
from the binary input function blocks (BxRBDR). Trip value recorder uses analog
information from the analog input function blocks (AxRADR). Disturbance recorder
DRPRDRE acquires information from both AxRADR and BxRBDR.
Default
Description
Hide
Indication mask for binary channel 15
Trig on 1
Trigger on positive (1) or negative (0) slope for
binary input 16
Hide
Indication mask for binary channel 16
1MRK 502 048-UUS A
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents