Monitored Data - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Name
Values (Range)
IHiHiLim
0.0 - 500.0
IHiLim
0.0 - 500.0
ILowLim
0.0 - 500.0
ILowLowLim
0.0 - 500.0
ILimHyst
0.000 - 100.000
FrDbRepInt
1 - 300
FrZeroDb
0 - 100000
FrHiHiLim
0.000 - 100.000
FrHiLim
0.000 - 100.000
FrLowLim
0.000 - 100.000
FrLowLowLim
0.000 - 100.000
FrLimHyst
0.000 - 100.000
UAmpComp5
-10.000 - 10.000
UAmpComp30
-10.000 - 10.000
UAmpComp100
-10.000 - 10.000
IAmpComp5
-10.000 - 10.000
IAmpComp30
-10.000 - 10.000
IAmpComp100
-10.000 - 10.000
IAngComp5
-10.000 - 10.000
IAngComp30
-10.000 - 10.000
IAngComp100
-10.000 - 10.000
14.1.2.5
Technical manual
Unit
Step
%IB
0.1
%IB
0.1
%IB
0.1
%IB
0.1
%
0.001
Type
1
m%
1
Hz
0.001
Hz
0.001
Hz
0.001
Hz
0.001
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
Deg
0.001
Deg
0.001
Deg
0.001

Monitored data

Table 349:
CVMMXN Monitored data
Name
Type
S
REAL
P
REAL
Q
REAL
Table continues on next page
Default
Description
150.0
High High limit in % of IBase
120.0
High limit in % of IBase
80.0
Low limit in % of IBase
60.0
Low Low limit in % of IBase
5.000
Hysteresis value in % of range (common for all
limits)
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
500
Zero point clamping
65.000
High High limit (physical value)
63.000
High limit (physical value)
47.000
Low limit (physical value)
45.000
Low Low limit (physical value)
5.000
Hysteresis value in % of range (common for all
limits)
0.000
Magnitude factor to calibrate voltage at 5% of
Vn
0.000
Magnitude factor to calibrate voltage at 30% of
Vn
0.000
Magnitude factor to calibrate voltage at 100%
of Vn
0.000
Magnitude factor to calibrate current at 5% of In
0.000
Magnitude factor to calibrate current at 30% of
In
0.000
Magnitude factor to calibrate current at 100%
of In
0.000
Angle calibration for current at 5% of In
0.000
Angle calibration for current at 30% of In
0.000
Angle calibration for current at 100% of In
Values (Range)
Unit
-
MVA
-
MW
-
MVAr
Section 14
Monitoring
Description
Apparent power magnitude of
deadband value
Active power magnitude of
deadband value
Reactive power magnitude of
deadband value
513

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents