Technical manual

Settings

The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
Position evaluation POS_EVAL
Identification
Function description
Position evaluation
Functionality
Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals OPENPOS or
CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
Function block
POS_EVAL
POSITION
OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd
IEC09000079 V1 EN
Figure 201:
POS_EVAL function block
Logic diagram
Position including quality
IEC08000469-1-EN V1 EN
Only the value, open/close, and status is used in this function. Time information is not
used.
IEC 61850
IEC 60617
identification
identification
POS_EVAL
-
POS_EVAL
POSITION
OPENPOS
CLOSEPOS
Section 12
Control
ANSI/IEEE C37.2
device number
-
Open/close position of
switch device
IEC08000469-1-en.vsd