The switching of the Local/Remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined
in the IED. Otherwise the default authority level, SuperUser, can handle the control
without LogOn. The users and passwords are defined in PCM600.

Local remote/Local remote control LOCREM/LOCREMCTRL

The function block Local remote (LOCREM) handles the signals coming from the local/
remote switch. The connections are seen in figure 178, where the inputs on function block
LOCREM are connected to binary inputs if an external switch is used. When the local
HMI is used, the inputs are not used and are set to FALSE in the configuration. The outputs
from the LOCREM function block control the output PSTO (Permitted Source To
Operate) on Bay control (QCBAY).
LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID
IEC09000208 V2 EN
Figure 178:
Configuration for the local/remote handling for a local HMI with one bay
and one screen page
The switching of the local/remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined
in the IED. Otherwise the default authority level, SuperUser, can handle the control
without LogOn. The users and passwords are defined in PCM600.
QCBAY
LR_ OFF
PSTO
LR_ LOC
UPD_ BLKD
LR_ REM
CMD_ BLKD
LR_ VALID
LOC
BL_ UPD
REM
BL_ CMD
LOCREMCTRL
PSTO1
HMICTR1
PSTO2
HMICTR2
PSTO3
HMICTR3
PSTO4
HMICTR4
PSTO5
HMICTR5
PSTO6
HMICTR6
PSTO7
HMICTR7
PSTO8
HMICTR8
PSTO9
HMICTR9
PSTO10
HMICTR10
PSTO11
HMICTR11
PSTO12
HMICTR12
IEC 09000208_1_en. vsd
Section 12
Control
379