1MRK 502 048-UUS A
Name
Values (Range)
Power2
0.0 - 500.0
Angle2
-180.0 - 180.0
TripDelay2
0.010 - 6000.000
Table 124:
GOPPDOP (32) Group settings (advanced)
Name
Values (Range)
k
0.00 - 0.99
Table 125:
GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
8.7.2.5
8.7.3
Technical manual
Unit
Step
%
0.1
Deg
0.1
s
0.001
Unit
Step
-
0.01
Unit
Step
-
1
-
-

Monitored data

Table 126:
GOPPDOP (32) Monitored data
Name
Type
P
REAL
PPERCENT
REAL
Q
REAL
QPERCENT
REAL
Directional underpower protection GUPPDUP (37)
Default
Description
1.0
Power setting for stage 2 in % of calculated
power base value
0.0
Characteristic angle for stage 2
1.000
Trip delay for stage 2
Default
Description
0.00
Low pass filter coefficient for power
measurement, V and I
Default
Description
1
Selection of one of the Global Base Value
groups
Pos Seq
Mode of measurement for current and voltage
Values (Range)
Unit
-
MW
-
%
-
MVAr
-
%
Section 8
Current protection
Description
Active Power
Active power in % of
calculated power base value
Reactive power
Reactive power in % of
calculated power base value
255