Signals - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
8.3.4
8.3.5
Table 98:
SDEPSDE (67N) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpMode
3I0Cosfi
3I03V0Cosfi
3I0 and fi
DirMode
Forward
Reverse
Table continues on next page
Technical manual

Signals

Table 96:
SDEPSDE (67N) Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKUN
BOOLEAN
Table 97:
SDEPSDE (67N) Output signals
Name
Type
TRIP
BOOLEAN
TRDIRIN
BOOLEAN
TRNDIN
BOOLEAN
TRUN
BOOLEAN
START
BOOLEAN
STDIRIN
BOOLEAN
STNDIN
BOOLEAN
STUN
BOOLEAN
STFW
BOOLEAN
STRV
BOOLEAN
STDIR
INTEGER
UNREL
BOOLEAN
Settings
Unit
Step
-
-
-
-
-
-
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Blocks the non-directional voltage residual outputs
Description
Common trip signal
Trip of the directional residual overcurrent
Trip of non-directional residual overcurrent
Trip of non-directional residual overvoltage
General pickup signal
Pick up of the directional residual overcurrent function
Pick up of non directional residual overcurrent
Pick up of non directional residual overvoltage
Pick up of directional function for fault in forward
direction
Pick up of directional function for fault in reverse
direction
Direction of fault
Residual voltage release of operation of directional
modes
Default
Description
Disabled
Operation Disable / Enable
3I0Cosfi
Selection of operation mode for protection
Forward
Direction of operation forward or reverse
Section 8
Current protection
223

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi