Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 6
Differential protection
6.1.2.4
Table 26:
T3WPDIF (87T) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IdMin
0.10 - 0.60
EndSection1
0.20 - 1.50
EndSection2
1.00 - 10.00
SlopeSection2
10.0 - 50.0
SlopeSection3
30.0 - 100.0
IdUnre
1.00 - 50.00
I2/I1Ratio
5.0 - 100.0
I5/I1Ratio
5.0 - 100.0
CrossBlockEn
Disabled
Enabled
NegSeqDiffEn
Disabled
Enabled
IMinNegSeq
0.02 - 0.20
Table continues on next page
88
Name
Type
PU_B
BOOLEAN
PU_C
BOOLEAN
BLK2H
BOOLEAN
BLK5H
BOOLEAN
BLKWAV
BOOLEAN
IDALARM
BOOLEAN
IDMAG_A
REAL
IDMAG_B
REAL
IDMAG_C
REAL
IBIAS
REAL
IDMAG_NS
REAL

Settings

Unit
Step
-
-
IB
0.01
IB
0.01
IB
0.01
%
0.1
%
0.1
IB
0.01
%
0.1
%
0.1
-
-
-
-
IB
0.01
Description
Pickup signal from phase B
Pickup signal from phase C
General second harmonic block signal
General fifth harmonic block signal
General block signal from waveform criteria
General alarm for sustained differential currents
Magnitude of fundamental frequency differential
current, phase A
Magnitude of fundamental frequency differential
current, phase B
Magnitude of fundamental frequency differential
current, phase C
Magnitude of the bias current, which is common to all
phases
Magnitude of the negative sequence differential current
Default
Description
Disabled
Operation Disable / Enable
0.30
Section 1 sensitivity current, usually W1
current
1.25
End of section 1, multiple of W1 rated current
3.00
End of section 2, multiple of W1 rated current
40.0
Slope in section 2 of operate-restrain
characteristics
80.0
Slope in section 3 of operate-restrain
characteristics
10.00
Unrestrained protection limit, multiple of W1
rated current
15.0
Maximum ratio of 2nd harmonic to fundamental
harmonic differential current
25.0
Maximum ratio of 5th harmonic to fundamental
harmonic differential current
Enabled
Operation Off/On for cross-block logic between
phases
Enabled
Operation Off/On for negative sequence
differential function
0.04
Minimum negative sequence current
1MRK 502 048-UUS A
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi