Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
9.2.5
Table 162:
OV2PTOV (59) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationStep1
Disabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
OpMode1
1 out of 3
2 out of 3
3 out of 3
Pickup1
1 - 200
t1
0.00 - 6000.00
t1Min
0.000 - 60.000
TD1
0.05 - 1.10
OperationStep2
Disabled
Enabled
OpMode2
1 out of 3
2 out of 3
3 out of 3
Pickup2
1 - 200
t2
0.000 - 60.000
Table 163:
OV2PTOV (59) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
ConnType
PhN DFT
PhN RMS
PhPh DFT
PhPh RMS
Technical manual

Settings

Unit
Step
-
-
-
-
-
-
-
-
%VB
1
s
0.01
s
0.001
-
0.01
-
-
-
-
%VB
1
s
0.001
Unit
Step
-
1
-
-
Default
Description
Disabled
Disable/Enable Operation
Enabled
Enable execution of step 1
Definite time
Selection of time delay curve type for step 1
1 out of 3
Number of phases required to operate (1 of 3, 2
of 3, 3 of 3) from step 1
120
Voltage start value (DT & IDMT) in % of VBase
for step 1
5.00
Definite time delay of step 1
5.000
Minimum operate time for inverse curves for
step 1
0.05
Time multiplier for the inverse time delay for
step 1
Enabled
Enable execution of step 2
1 out of 3
Number of phases required to operate (1 of 3, 2
of 3, 3 of 3) from step 2
150
Voltage start value (DT & IDMT) in % of VBase
for step 2
5.000
Definite time delay of step 2
Default
Description
1
Selection of one of the Global Base Value
groups
PhN DFT
Group selector for connection type
Section 9
Voltage protection
289