Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 17
Basic IED functions
17.10.5
Table 519:
3PHSUM Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
SummationType
Group1+Group2
Group1-Group2
Group2-Group1
-(Group1+Group2)
DFTReference
InternalDFTRef
DFTRefGrp1
External DFT ref
Table 520:
3PHSUM Non group settings (advanced)
Name
Values (Range)
FreqMeasMinVal
5 - 200
17.10.6
17.11
696
Table 518:
3PHSUM Output signals
Name
Type
AI3P
GROUP SIGNAL
AI1
GROUP SIGNAL
AI2
GROUP SIGNAL
AI3
GROUP SIGNAL
AI4
GROUP SIGNAL

Settings

Unit
Step
-
1
-
-
-
-
Unit
Step
%
1
Operation principle
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal matrix
for analog inputs function (SMAI). In the same way, the BLOCK input will reset all the
outputs of the function to 0.
Global base values GBASVAL
Description
Linear combination of two connected three phase inputs
Linear combination of input 1 signals from both SMAI
blocks
Linear combination of input 2 signals from both SMAI
blocks
Linear combination of input 3 signals from both SMAI
blocks
Linear combination of input 4 signals from both SMAI
blocks
Default
Description
1
Selection of one of the Global Base Value
groups
Group1+Group2
Summation type
InternalDFTRef
DFT reference
Default
Description
10
Magnitude limit for frequency calculation in %
of Vbase
1MRK 502 048-UUS A
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents