Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
7.4.5
Table 72:
OOSPPAM (78) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationZ1
Disabled
Enabled
ReachZ1
1.00 - 100.00
OperationZ2
Disabled
Enabled
tBreaker
0.000 - 1.000
Table 73:
OOSPPAM (78) Group settings (advanced)
Name
Values (Range)
NoOfSlipsZ1
1 - 20
NoOfSlipsZ2
1 - 60
tReset
1.000 - 60.000
Technical manual
Table 71:
OOSPPAM (78) Output signals
Name
Type
TRIP
BOOLEAN
TRIPZ1
BOOLEAN
TRIPZ2
BOOLEAN
START
BOOLEAN
GENMODE
BOOLEAN
MOTMODE
BOOLEAN
R
REAL
X
REAL

Settings

Unit
Step
-
-
-
-
-
0.01
-
-
s
0.001
Unit
Step
-
1
-
1
s
0.001
Description
Common trip, issued when either zone 1 or zone 2 trip
Zone 1 trip
Zone 2 trip
Set when measured impedance enters lens
characteristic
Generator rotates faster than the system during pole slip
Generator rotates slower than the system during pole
slip
Real part of measured positive-sequence impedance %
of VBase/(sqrt(3)*IBase)
Imaginary part of measured positive-seq impedance %
of VBase/(sqrt(3)*IBase)
Default
Description
Disabled
Operation Enable/Disable
Enabled
Operation Zone1 Enable/disable
50.00
Percentage part of total forward impedance;
defines Z1 reach
Enabled
Operation Zone2 Enable/disable
0.040
Breaker opening time; use default 0s value if it
is unknown
Default
Description
1
Number of pole-slips in zone 1 required for
zone 1 trip
3
Number of pole-slips in zone 2 required for
zone 2 trip
6.000
Time without any slip required to completely
reset function
Section 7
Impedance protection
175