Monitored Data - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Name
Values (Range)
tUN
0.000 - 60.000
INRel>
0.25 - 200.00
UNRel>
1.00 - 300.00
Table 99:
SDEPSDE (67N) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
8.3.6
8.3.7
8.3.7.1
Technical manual
Unit
Step
s
0.001
%IB
0.01
%VB
0.01
Unit
Step
-
1

Monitored data

Table 100:
SDEPSDE (67N) Monitored data
Name
Type
INCOSPHI
REAL
IN
REAL
UN
REAL
SN
REAL
ANG FI-RCA
REAL
Operation principle
Function inputs
The function is using phasors of the residual current and voltage. Group signals I3P and
V3P containing phasors of residual current and voltage is taken from pre-processor
blocks.
The sensitive directional ground fault protection has the following sub-functions
included:
Default
Description
0.100
Time delay for non-directional residual
overvoltage
1.00
Residual release current for all directional
modes, in % of IBase
3.00
Residual release volt for all dir modes, % of
VBase
Default
Description
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
-
A
-
A
-
kV
-
MVA
-
deg
Section 8
Current protection
Description
Mag of residual current along
polarizing qty 3I0cos(Fi-RCA)
Measured magnitude of the
residual current 3I0
Measured magnitude of the
residual voltage 3V0
Measured magnitude of
residual power 3I03V0cos(Fi-
RCA)
Angle between 3V0 and 3I0
minus RCA (Fi-RCA)
225