Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
12.1.5
Table 210:
SESRSYN (25) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CBConfig
No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
VRatio
0.500 - 2.000
PhaseShift
-180 - 180
OperationSynch
Disabled
Enabled
FreqDiffMin
0.003 - 0.250
FreqDiffMax
0.050 - 0.500
FreqRateChange
0.000 - 0.500
tBreaker
0.000 - 60.000
tClosePulse
0.050 - 60.000
tMaxSynch
0.00 - 6000.00
tMinSynch
0.000 - 60.000
OperationSC
Disabled
Enabled
VDiffSC
0.02 - 0.50
FreqDiffA
0.003 - 1.000
FreqDiffM
0.003 - 1.000
PhaseDiffA
5.0 - 90.0
PhaseDiffM
5.0 - 90.0
tSCA
0.000 - 60.000
tSCM
0.000 - 60.000
Table continues on next page
Technical manual

Settings

Unit
Step
-
-
-
-
-
0.001
Deg
1
-
-
Hz
0.001
Hz
0.001
Hz/s
0.001
s
0.001
s
0.001
s
0.01
s
0.001
-
-
pu
0.01
Hz
0.001
Hz
0.001
Deg
1.0
Deg
1.0
s
0.001
s
0.001
Default
Description
Disabled
Disable/Enable Operation
No voltage sel.
Select CB configuration
1.000
Multiplication factor for minor internal
adjustmernt of measured line voltage for
synchro functions
0
Additional phase angle for selected line voltage
Disabled
Operation for synchronizing function Off/On
0.010
Minimum frequency difference limit for
synchronizing
0.200
Maximum frequency difference limit for
synchronizing
0.300
Maximum allowed frequency rate of change
0.080
Closing time of the breaker
0.200
Breaker closing pulse duration
600.00
Resets synch if no close has been made before
set time
2.000
Minimum time to accept synchronizing
conditions
Enabled
Operation for synchronism-check function
Off/On
0.15
Voltage difference limit for synchrocheck in p.u
of set voltage base value
0.010
Frequency difference limit between bus and
line Auto
0.010
Frequency difference limit between bus and
line Manual
25.0
Phase angle difference limit between bus and
line Auto
25.0
Phase angle difference limit between bus and
line Manual
0.100
Time delay output for synchrocheck Auto
0.100
Time delay output for synchrocheck Manual
Section 12
Control
349