Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
12.3.8.6
12.3.9
12.3.9.1
12.3.9.2
Technical manual
Table 256:
DB_LINE (3) Output signals
Name
Type
989REL
BOOLEAN
989ITL
BOOLEAN
389GREL
BOOLEAN
389GITL
BOOLEAN
989GREL
BOOLEAN
989GITL
BOOLEAN

Settings

The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
Interlocking for line bay ABC_LINE (3)
Identification
Function description
Interlocking for line bay
Functionality
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 197. The function
can also be used for a double busbar arrangement without transfer busbar or a single
busbar arrangement with/without transfer busbar.
Description
Switching of 989 is allowed
Switching of 989 is not allowed
Switching of 389G is allowed
Switching of 389G is not allowed
Switching of 989G is allowed
Switching of 989G is not allowed
IEC 61850
IEC 60617
identification
identification
ABC_LINE
-
Section 12
Control
ANSI/IEEE C37.2
device number
3
425