Section 17
Basic IED functions
17.7.3
17.8
17.8.1
17.8.2
17.8.3
Table 508:
PRIMVAL Non group settings (basic)
Name
Values (Range)
Frequency
50.0 - 60.0
PhaseRotation
Normal=ABC
Inverse=ACB
17.9
17.9.1
686

Settings

The function does not have any parameters available in the local HMI or PCM600.
Primary system values PRIMVAL
Identification
Function description
Primary system values
Functionality
The rated system frequency and phasor rotation are set under Main menu/
Configuration/ Power system/ Primary values/PRIMVAL in the local HMI and
PCM600 parameter setting tree.
Settings
Unit
Step
Hz
10.0
-
-
Signal matrix for analog inputs SMAI
Functionality
Signal matrix for analog inputs function (SMAI), also known as the preprocessor
function, processes the analog signals connected to it and gives information about all
aspects of the analog signals connected, like the RMS value, phase angle, frequency,
harmonic content, sequence components and so on. This information is then used by the
respective functions in ACT (for example protection, measurement or monitoring).
The SMAI function is used within PCM600 in direct relation with the Signal Matrix tool
or the Application Configuration tool.
IEC 61850
IEC 60617
identification
identification
PRIMVAL
-
Default
Description
50.0
Rated system frequency
Normal=ABC
System phase rotation
1MRK 502 048-UUS A
ANSI/IEEE C37.2
device number
-
Technical manual