1MRK 502 048-UUS A
12.12.3
12.12.4
Table 289:
I103GENCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
PulseLength
0.000 - 60.000
InfNo
1 - 255
12.13
12.13.1
Technical manual

Signals

Table 287:
I103GENCMD Input signals
Name
Type
BLOCK
BOOLEAN
Table 288:
I103GENCMD Output signals
Name
Type
CMD_OFF
BOOLEAN
CMD_ON
BOOLEAN
Settings
Unit
Step
-
1
s
0.001
-
1
IED commands with position and select for IEC
60870-5-103 I103POSCMD
Functionality
I103POSCMD has double-point position indicators that are getting the position value as
an integer (for example from the POSITION output of the SCSWI function block) and
sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not define
the use of values 0 and 3 . However, when connected to a switching device, these values
are transmitted.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used to
indicate that the monitored apparatus has been selected (in a select-before-operate type of
control)
Default
Description
0
Block of command
Description
Command output OFF
Command output ON
Default
Description
1
Function type (1-255)
0.400
Pulse length
1
Information number for command output
(1-255)
Section 12
Control
465