ABB Relion Technical Manual page 354

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 12
Control
348
Name
Type
TSTENOK
BOOLEAN
VSELFAIL
BOOLEAN
B1SEL
BOOLEAN
B2SEL
BOOLEAN
L1SEL
BOOLEAN
L2SEL
BOOLEAN
SYNPROGR
BOOLEAN
SYNFAIL
BOOLEAN
FRDIFSYN
BOOLEAN
FRDERIVA
BOOLEAN
VOKSC
BOOLEAN
VDIFFSC
BOOLEAN
FRDIFFA
BOOLEAN
PHDIFFA
BOOLEAN
FRDIFFM
BOOLEAN
PHDIFFM
BOOLEAN
INADVCLS
BOOLEAN
VDIFFME
REAL
FRDIFFME
REAL
PHDIFFME
REAL
Vbus
REAL
VLine
REAL
MODEAEN
INTEGER
MODEMEN
INTEGER
Description
Energizing check OK test output
Selected voltage transformer fuse failed
Bus1 selected
Bus2 selected
Line1 selected
Line2 selected
Synchronizing in progress
Synchronizing failed
Frequency difference out of limit for synchronizing
Frequency derivative out of limit for synchronizing
Voltage magnitudes above set limits
Voltage difference out of limit
Frequency difference out of limit for Auto operation
Phase angle difference out of limit for Auto operation
Frequency difference out of limit for Manual operation
Phase angle difference out of limit for Manual Operation
Inadvertent circuit breaker closing
Calculated difference of voltage in p.u of set voltage
base value
Calculated difference of frequency
Calculated difference of phase angle
Bus voltage
Line voltage
Selected mode for automatic energizing
Selected mode for manual energizing
1MRK 502 048-UUS A
Technical manual