20 Technical data
20.1.2

Temperature measurement input (IN 5)

Probe-/Signal type
Pt100 DIN EN 60751
Pt1000 DIN EN 60751
Resistance transmitter
RTD temperature probe
with customer-specific
c
characteristic line
up to 400 Ω
to 4000 Ω
to 100 kΩ
NTC 8k55
NTC 22k
Sensor lead resistance
Lead compensation
a
MR: measuring range span
b
R
: total resistance of the resistance transmitter/Resistance potentiometer
Tot
c
Customer-specific linearization can be used to enter a sensor characteristic line.
d
R
: maximal resistance across the measuring range (400
max
20.1.3

Universal input (IN 6)

Signal type
Current signal
a
MR: measuring range span
20.1.4

Measuring circuit monitoring base unit

Inputs
Temperature input
Universal input (current signal)
112
Connection type
2-wire/3-wire
2-wire/3-wire
3-wire
2-wire/3-wire
2-wire/3-wire
2-wire/3-wire
2-wire/3-wire
2-wire/3-wire
maximal 30 Ω per line with 3-wire circuit
Not required for 3-wire circuit. With a 2-wire circuit, lead calibration can
be executed at the respective input by means of an measured value cor-
rection with the aid of the "Offset" setting.
Measuring
Measuring accu-
range
racy
-200 to +850 °C ≤ 0.05 % of MR
-200 to +850 °C ≤ 0.1 % of MR
0 to 100 kΩ
0.5 % of R
0 to 400 Ω
≤ 0.1 % of R
0 to 4000 Ω
0 to 100 kΩ
≤ 0.1 % of R
0 to 150 °C
0 to 150 °C
Ω
4000 W or 100 kW)
,
Measuring
Measuring accu-
range
racy
0(4) to 20 mA
0.1 % of MR
Underrange/
overrange
Yes
Yes
Ambient
temperature
influence
a
≤ 50 ppm/K
a
≤ 50 ppm/K
b
≤ 100 ppm/K
Tot
d
≤ 100 ppm/K
max
d
≤ 100 ppm/K
max
Ambient
temperature
influence
a
100 ppm/K