Analog Outputs Of Base Unit And Optional Boards; Digital Inputs Base Unit; Digital Inputs Optional Boards; Digital Outputs, Power Supply Unit Board - JUMO AQUIS touch S Assembly Instructions Manual

Modular multichannel measuring device for liquid analysis with integrated controller and paperless recorder
Hide thumbs Also See for AQUIS touch S:
Table of Contents

Advertisement

20 Technical data
20.3

Analog outputs of base unit and optional boards

Signal type
Voltage signal
Current signal
20.4

Digital inputs base unit

Description
Input frequency
ranges
b
≤ 1 Hz
IN 1
b,c
≤ 1 Hz
IN 2 to 3
Switching sig-
nal
b,c
IN 2 to 3
3 to 300 Hz
Flow
300 Hz to 10 kHz
a
This specification is relevant only if the Ext. voltage supply is selected under the "Contact" point in the
Configuration. Sensors and transmitters should be supplied from voltage supply outputs on the JUMO
AQUIS touch S. An externally supplied voltage signal must not have a voltage over 28 V.
b
All digital inputs IN 1 to 3 are suitable for connecting proximity switches. Recommended
types are: Wachendorff P2C2B1208NO3A2 and Balluff BES M12EG-PSC80F-BP03.
c
Binary inputs IN 2 and IN 3 can be used for impeller flow-through sensors (water meters) or
magnetic-inductive flow-through meters (square-wave signal), for example. The input frequency depends
on the configured measurement principle in the flow function.
20.5

Digital inputs optional boards

Max. number of retrofittable
digital inputs
max. 2 optional boards with 3 digi-
tal inputs each
20.6

Digital outputs, power supply unit board

Description
OUT 1
OUT 2
OUT 3
a
The maximal ampacity of the contacts must not be exceeded.
118
Signal range
0 to 10 V
0/4 to 20 mA
Min. pulse dura-
tion
On
Off
300 ms
300 ms
30 μs
30 μs
30 μs
30 μs
Max.
pulse frequen-
cy
1 Hz
Switching out-
put
Relay, normally
open contact
Relay, normally
open contact
Relay
changeover
contact
Admissible
Accuracy
load resistance
> 500 Ω
≤ 0.25 %
< 450 Ω
≤ 0.25 %
Signal type
Configurable as:
potential-free con-
tact,
or
ext. voltage supply
(maximal 28 V)
Min. pulse dura-
tion
On
Off
300 ms
300 ms
Ampacity at resis-
tive load
3 A at AC 250 V
Ambient tem-
perature in-
fluence
≤ 100 ppm / K
≤ 100 ppm / K
Switching thresh-
a
olds
On
Off
> 8 V
< 5 V
> 1.8 mA
< 1.2 mA
Signal type
Potential-free contact
a
Contact life
150,000 switching cy-
cles