Configuration point Selection/
Alarm type
Alarm/Event list
Alarm text
Limit value
Hysteresis
Window range
Pulse function
Pulse time
Alarm delay
On
Alarm delay Off
setting option
inactive
minimum alarm
maximum alarm
alarm window
invert alarm window
only for
CR analysis inputs:
USP
Pre-alarm USP
purified water
purified water pre-alarm
off
event
alarm
up to 21 text characters
-99999 to +99999
0 to 99999
0 to 99999
Yes
No
0 to 999 s
0 to 999 s
0 to 999 s
10 Configuration
Explanation
Four alarm types (comparator functions) can be
selected to monitor measured values for violation
of limit values.
Characteristic lines after the table
Limit value alarms to USP <645> or
European Pharmacopoeia (Ph. Eur.) for
cleaned water
Assignment of alarm notification to alarm list or
event list
Text for the alarm/event list
Limit value for the particular alarm type
Spacing between switch-on and switch-off points
for the alarm types
Characteristic lines after the table
Range of the alarm window
Characteristic lines after the table
Time limit for alarm with the wiper time as maxi-
mum alarm duration
Duration of alarm with pulse function activated
Time delay between occurrence of the alarm
condition and triggering of the alarm
Time delay between ending of the alarm condi-
tion and clearing of the alarm