10 Configuration
10.7
Analog outputs of base unit and optional boards
Configuration point Selection/
Description
Signal
output value
Analog signal
Enable manu. mode
Safety value 1 to 4
Scale start 1 to 4
Scale end 1 to 4
Digital signal for hold Selection from
28
Open: Device Menu > Configuration > Analog Outputs >
Analog Output 1 to 9
setting option
up to 15 text characters
Selection from
analog selection
0 to 10 V
0 to 20 mA
4 to 20 mA
10 to 0 V
20 to 0 mA
20 to 4 mA
Yes
No
0 to 10.7 V
or
0 to 22 mA
-99999 to +99999
-99999 to +99999
binary selector
Explanation
Designation for the output
Analog signal source of the output
Type of standard signal to be generated
The manual mode for the specific output is en-
abled/locked here.
The manual mode permits fixed analog values
to be set for the output for testing purposes.
⇨
Chapter 8.2.3 "Functional level", page 93
Specifies an analog value that the output as-
sumes at hold, at calibration or in case of a fault
If an analysis input for conductivity measurement
is set as "Signal output value", the safety values
1 to 4 are assigned to conductivity measuring
ranges 1 to 4. Pairs with the same number be-
long together.
Otherwise, the safety value 1 applies.
a
Analog value of the analog signal source (see
configuration item "Signal output value") that cor-
responds to the lower limit of the standard signal
range generated
a
Analog value of the analog signal source (see
configuration item "Signal output value") that cor-
responds to the upper limit of the standard
signal range generated (10 V or 20 mA)
Digital signal for activating the hold function
When the hold function is activated, the analog
output assumes the state defined in the "Re-
sponse at hold" setting.
[
]
0 V or 0(4) mA