4.3.8 Trend Recording Mode Configuration

The Model 8335 has a recording function key
calculated values (Urms, Vrms, Arms, etc.). Four independent configurations can
be configured as needed.
Choose the configuration by pressing the yellow button corresponding to the
icons
1
Next, move through the choices with the ◄ and ► buttons and select the
desired parameters with the ▲ and ▼ buttons. As you move through the
parameters, each choice, in turn, will be highlighted.
To activate the selected parameter to record, use the
The selected parameters will have a filled in
have an unfilled
The recordable values are:
Value
Description
Urms
Phase-to-phase voltage (2φ, 3φ)
Vrms
Phase-to-neutral voltage
Arms
Phase A, B, C, N
W
Active power
PF
Power factor
Uthd
Harmonic distortion of line voltage (2φ, 3φ)
Vthd
Full harmonic distortion of phase-to-neutral voltage
Athd
Full harmonic distortion of current
VAR
Reactive power
DPF
Displacement factor
Ucf
Crest factor of phase voltage (2φ, 3φ)
Vcf
Crest factor of phase-to-neutral voltage
Acf
Crest factor of current
VA
Apparent power
Shop for AEMC products online at:
Tan
Tangent
46
Figure 4-13
2
3
4
.
.
PowerMeterStore
www.
for recording measured and
button.
and those not selected will
.ca
Power Quality Analyzer Model 8335
1.877.766.5412