Power Supply - AEMC 8335 Power Pad User Manual

3-phase power quality analyzer
Table of Contents

Advertisement

supply voltage. In any case, disconnect the primary measurement transformer
circuit from the supply network.
3.
Connect each CT secondary to the input of the 5A adapter in the correct order
(ground on P2) and the right phase order L1, L2, L3.
Adapter Box Specifications (add PowerPad® accuracy ±0.5% ± 1ct):
Note: Currents < (Primary x 5) ÷ (Secondary x 1000) will be displayed as zero
on the PowerPad
Range:
Output / Input Ratio:
Dimensions:
Weight:
Impermeability:
Electrical safety:
Operating Temperature: 5° to 131°F (-15° to 55°C), 0 to 90% RH
Storage Temperature:
Reference Conditions: 73°F (23°C) ±3K, 50 to 85% RH, 50/60Hz ±2Hz
Current measurement according to IEC 44-1 Class 0.5
Range
Error %
Phase Error
Primary Voltage Loss: < 0.3V
Permanent Overload:
Temperature Influence: < 0.1% par 25K
Frequency Influence
Error
Phase error

3.2.7 Power Supply

AC Power (external power supply) - 600V CAT IV; 1000V CAT III
Operating Range: 230V
Max Power: 65VA
Shop for AEMC products online at:
32
with this probe.
®
5A
0.2mV/mA
6.00 x 3.74 x 3.38" (153 x 95 x 86mm)
1.98 lbs (900g)
IP50 per EN 60529 (electrical IP2X for the terminals)
Double Insulation, 300V CAT III
Pollution Degree 2 per IEC 61010-1
-40° to 185°F (-40° to 85°C), 0 to 90% RH
5mA to 50mA
0.35% + 1.5mA
0.5°
10A
65Hz to 500Hz
0.1%
0.1°
AC
PowerMeterStore
www.
AC
50mA to 1A
0.25% + 1mA
0.4°
500Hz to 1kHz
0.3%
0.2°
± 10% @ 50Hz and 120V
Power Quality Analyzer Model 8335
1A to 6A
0.25% + 0.5mA
0.33°
1kHz to 5kHz
0.5%
± 10% @ 60Hz
AC
1.877.766.5412
.ca