Accuracy Specifications (Excluding Current Probes) - AEMC 8335 Power Pad User Manual

3-phase power quality analyzer
Table of Contents

Advertisement

3.2.3 Accuracy Specifications (excluding current probes)

Measurement
Frequency
Simple
RMS
Voltage
(5)
Compound
Simple
Direct
Voltage
(DC)
(6)
Compound
SR clamp
MR clamp
MN93 clamp
SL261 clamp
(10mV/A)
MN193 clamp
(100A)
RMS
Current
(5)
SL261 clamp
(100mV/A)
MN93A clamp (5A)
5A adapter
AmpFlex
MiniFlex
Shop for AEMC products online at:
20
Measurement range
without ratio
(with unity ratio)
Min
40 Hz
1 V
1 V
1 V
1 V
1 A
0.2 A
0.1 A
0.01 A
0.005 A
®
10 A
®
PowerMeterStore
www.
Resolution
(with unity ratio)
Max
70 Hz
0.01 Hz
0.1 V
V < 1000 V
1200 V
(1)
1 V
V ≥ 1000 V
0.1 V
U < 1000 V
2400 V
(2)
1 V
U ≥ 1000 V
0.1 V
V < 1000 V
1697 V
(3)
1 V
V ≥ 1000 V
0.1 V
U < 1000 V
3394 V
(4)
1 V
U ≥ 1000 V
0.1 A
A < 1000 A
1200 A
1 A
A ≥ 1000 A
240 A
0.1 A
0.01 A
A < 100 A
120 A
0.1 A
A ≥ 100 A
0.001 A
A < 10 A
12 A
0.01 A
A ≥ 10 A
6 A
0.001 A
0.1 A
A < 1000 A
6500 A
1 A
A ≥ 1000 A
Power Quality Analyzer Model 8335
Accuracy
±(0.01 Hz)
±(0.5% + 0.2 V)
±(0.5% + 1 V)
±(0.5% + 0.2 V)
±(0.5% + 1 V)
±(1% + 0.5 V)
±(1% + 1 V)
±(1% + 0.5 V)
±(1% + 1 V)
±(0.5% + 0.2 A)
±(0.5% + 1 A)
±(0.5% + 0.2 A)
±(0.5% + 0.02 A)
±(0.5% + 0.1 A)
±(0.5% + 0.002 A)
±(0.5% + 0.01 A)
±(0.5% + 0.002 A)
±(0.5% + 1 A)
1.877.766.5412
.ca

Advertisement

Table of Contents
loading

This manual is also suitable for:

8335Powerpad