AEMC 8335 Power Pad User Manual page 26

3-phase power quality analyzer
Table of Contents

Advertisement

Apparent energy
(1) The stated uncertainties on the active power and energy measurements are max for |cos F| = 1 and
typical for the other phase differences.
(2) The stated uncertainties on the reactive power and energy measurements are max for |sin F| = 1
and typical for the other phase shifts.
(3) With MN193 clamp (5A) or 5A adapter.
(4) With AmpFlex
or MiniFlex
®
(5) The resolution depends on the current sensor used and on the value to be displayed.
(6) The energy is equivalent to more than 146 years of the associated maximum power (unity ratios).
Measurement
Phase differences
of fundamentals
cos F
(DPF)
tan F
Unbalance
(UNB)
(1) |tan F| = 32,767 corresponds to F = ±88.25° + k × 180° (k being a natural number)
Measurement
Voltage Harmonic
Ratio (t)
Current Harmonic
Ratio (t)
(excluding
AmpFlex
®
& MiniFlex
)
®
Current Harmonic
Ratio (t)
(AmpFlex
®
& MiniFlex
)
®
Total Voltage
Harmonic Distortion
THD (THD-F)
Shop for AEMC products online at:
24
9,999,999
1 mVAh
MVAh
.
®
Measurement Range
Min
Max
-179°
180°
-1
1
-32.77
32.77
(1)
0%
100%
Measurement Range
Min
Max
0%
1600%
0%
1600%
0%
1600%
0%
999.9%
PowerMeterStore
www.
7 digits at most
(6)
Resolution
0.001
0.001
tan F < 10
(1)
0.01
tan F ≥ 10
0.1%
Resolution
0.1%
t < 999.9%
1%
t ≥ 1000%
0.1%
t < 999.9%
1%
t ≥ 1000%
0.1%
t < 999.9%
1%
t ≥ 1000%
0.1%
Power Quality Analyzer Model 8335
±(1%)
(5)
Accuracy
±(2°)
±(1°) for F
±(5 ct) for DPF
±(1°) for F
±(1%)
Accuracy
±(2.5 % + 5 ct)
±(2% + (n × 0.2%) + 5 ct)
n ≤ 25
±(2% + (n × 0.5%) + 5 ct)
n > 25
±(2% + (n × 0.3%) + 5 ct)
n ≤ 25
±(2% + (n × 0.6%) + 5 ct)
n > 25
±(2.5% + 5 ct)