Measurement Of Min, Max, Average, Voltage And Current Values - AEMC 8335 Power Pad User Manual

3-phase power quality analyzer
Table of Contents

Advertisement

Item
Function
Instantaneous value cursor; change values with the cursor using the ◄ and ► buttons
1
2
Peak factor for each curve
Instantaneous value of the signals at the intersection of the cursor and the graphs
t: time relative to the start of the period (expressed in milliseconds)
3
A1: instantaneous current of phase 1
A2: instantaneous current of phase 2
A3: instantaneous current of phase 3
Note: L1, L2 and L3 display the peak factors of the current and of the voltage
respectively for phases 1, 2 and 3.
5.3.4 Measurement of Min, Max, Average, Voltage and
Current Values
This sub-menu displays the RMS, maximum, minimum and average values for
voltage and current, together with those for the instantaneous positive and nega-
tive voltage and current peaks.
NOTE: The display screen varies depending on which value is selected.
3U: Displays the one-second mean and half-cycle maximum and minimum RMS
values and the instantaneous positive and negative phase-to-phase voltage peaks.
4V: Displays the one-second mean and half-cycle maximum and minimum RMS
values and the instantaneous positive and negative peaks of the phase-to-neutral
voltages and of the neutral.
4A: Displays the one-second mean and half-cycle maximum and minimum RMS
values and the positive and negative instantaneous peak values of the phase and
neutral currents.
L1/L2/L3: Displays the one-second mean and half-cycle maximum and minimum
RMS values and the instantaneous positive and negative peaks of the phase-to-
neutral voltage and of the current of phase 1.
N: Displays the RMS values and the positive and negative instantaneous peaks of
the neutral relative to earth.