AEMC 8335 Power Pad User Manual page 28

3-phase power quality analyzer
Table of Contents

Advertisement

Measurement
Simple
RMS
Harmonic
Voltage
(order n ≥ 2)
Compound
SR clamp
MR clamp
MN93 clamp
SL261 clamp
(10mV/A)
MN193 clamp
(100A)
SL261 clamp
RMS
(100mV/A)
Harmonic
Current
MN193 clamp
(order n ≥ 2)
(5A)
5A adapter
AmpFlex
& MiniFlex
AmpFlex
& MiniFlex
(1) In 1000 V
, CAT III, provided that the voltage between each of the terminals and earth does not
rms
exceed 1000 V
rms
(2) Two-phase (opposite phases) – same note as (1).
(3) RMS value of the fundamental.
Shop for AEMC products online at:
26
Measurement
range
(with unity ratio)
Min
1 V
1 V
1 A
0.2 A
0.1 A
0.01 A
®
0.005 A
®
®
10 A
®
.
PowerMeterStore
www.
Resolution
(with unity
ratio)
Max
0.1 V
V < 1000 V
1200 V
(1)
1 V
V ≥ 1000 V
0.1 V
U < 1000 V
2400 V
(2)
1 V
U ≥ 1000 V
0.1 A
A < 1000 A
1200 A
1 A
A ≥ 1000 A
240 A
0.1 A
0.01 A
A < 100 A
120 A
0.1 A
A ≥ 100 A
0.001 A
A < 10 A
12 A
0.01 A
A ≥ 10 A
6 A
0.001 A
0.1 A
A < 1000 A
6500 A
1 A
A ≥ 1000 A
Power Quality Analyzer Model 8335
Accuracy
±(2.5 % + 1 V)
±(2.5 % + 1 V)
±(2% + (n x 0.2%) + 1 A)
n ≤ 25
±(2% + (n x 0.5%) + 1 A)
n > 25
±(2% + (n x 0.2%) + 1 A)
n ≤ 25
±(2% + (n x 0.5%) + 1 A)
n > 25
±(2% + (n x 0.2%) + 0.1 A)
n ≤ 25
±(2% + (n x 0.5%) + 0.1 A)
n > 25
±(2% + (n x 0.2%) + 0.01 A)
n ≤ 25
±(2% + (n x 0.5%) + 0.01 A)
n > 25
±(2% + (n x 0.2%) + 0.01 A)
n ≤ 25
±(2% + (n x 0.5%) + 0.01 A)
n > 25
±(2% + (n x 0.3%) + 1 A +
(Af
x 0.1%))
(3)
rms
n ≤ 25
±(2% + (n x 0.6%) + 1 A +
(Af
x 0.1%))
(3)
rms
n > 25
1.877.766.5412