(excluding AmpFlex
SR clamp
MR clamp
MN93 clamp
SL261 clamp (10mV/A)
SL261 clamp (100mV/A)
MN193 clamp (100A)
MN193 clamp (5A)
5 A adapter
3.2 Electrical Specifications
Sampling Frequency (256 samples per cycle):
12.8kHz samples/sec per channel @ 50Hz
15.36kHz samples/sec per channel @ 60Hz
Waveforms: Displays voltages and currents
Screen Captures: 50 max
Transients: Detection and recording of transients (up to 210)
Inrush Current: Detection and recording of Inrush current (1 max)
Memory: 2GB with date and time programming
Alarm Function: 10,000 alarms max
3.2.1 Voltage Inputs
Range for use: 0 to 1000 Vrms AC+DC phase-to-neutral and neutral-to-earth
(on condition of compliance with 1000 Vrms with respect to earth in CAT III)
Input Impedance: 969 kW (between phase and neutral and neutral and earth)
Admissible Overload: 1200 Vrms constant
3.2.2 Current Inputs
Operating Range: 0 to 1V
Input Impedance: 1MW for current probe circuit
Shop for AEMC products online at:
Overload: 1.7V
Power Quality Analyzer Model 8335
Current Sensor
& MiniFlex
®
0 to 2000 Vrms AC+DC phase-to-phase
2000 Vrms for one second
PowerMeterStore
12.4kW for AmpFlex
www.
Nominal RMS current
)
(A
®
and MiniFlex
circuit
®
®
) [A]
nom
1000
1000
200
100
10
100
5
5
1.877.766.5412
.ca
19