OUT
= Temperature Set Point
n
Using the LCD:
SP
+ OUT
kp1
where k
=11,12,13,14,21,22,23,24,31,32,33,34 (set point number) and
p1
n=1,2,3,4,5,6 (Output number)
SP
+ OUT
kp2
where k
=11,12,13,14,21,22,23,24,31,32,33,34 and n=1,2,3,4,5,6
p2
Using RS232: kk
1
where kk
=Setting line # and n=1,2,3,4,5,6
1
Kk
/0/1/n
2
To invert a single assigned setpoint, simply invert the setting as follows:
Using the LCD: !SP
where kl= ,12,13,14,21,22,23,24,31,32,33,34 and n=1,2,3,4,5,6
Using RS232: kk/1/0/n
where k=Parameter # and n=1,2,3,4,5,6
NOTE: Do not use the inversion operator on individual set points when
remote control through DNP3.0 or MODBUS and fail-safe cooling control is
desired. The INVERT setting must be used on each output requiring fail-
safe cooling control when remote cooling control through DNP3.0 or
MODBUS is required. The use of the inversion operator on a set point will
not be recognized by the remote control functions resulting in the cooling
to be de-energized.
To control a bank using two set points in fail-safe:
Using the LCD:
SP
+ OUT
kp1
where k
=,12,13,14,21,22,23,24,31,32,33,34 and n=1,2,3,4,5,6
p1
SP
+ OUT
kp2
where k
=,12,13,14,21,22,23,24,31,32,33,34 and n=1,2,3,4,5,6
p2
Using RS232:
kk
/0/1/n where kk
1
kp1
n
n
/0/1/n
where kk
=Parameter # and n=1,2,3,4,5,6
2
OUT
kl
n
n
n
=Parameter # and n=1,2,3,4,5,6
1
+ Temperature Set Point
66
kp2
V6.70 20131017