Category
"Status"
LED
Start error
Operation
Operation
Operation
Operation
Operation
"BusError"
Meaning
LED
Incompatible module on
system bus
No firmware present in
module
Incorrect (incompatible)
hardware (actual/target)
Incorrect (incompatible)
hardware VdN (actual/tar-
get)
Incorrect (incompatible)
software in module (actual/
target)
Incorrect (incompatible)
software in module (incom-
patible with central pro-
cessing unit)
Incorrect (incompatible)
software in module (incom-
patible with hardware)
Incorrect (incompatible)
software VdN in module
(actual/target)
Optional board 1 incorrect
(actual/target)
Optional board 2 incorrect
(actual/target)
Optional board 3 incorrect
(actual/target)
---
Calibration mode
---
DHCP error (no IP
address)
Battery pre-warning/bat-
tery dead (after "cold"
reset, see "Buffer battery
dead" start error)
PLC program not available.
---
System in "Run" (OP) state
– no error
---
System in "Stop" (INIT)
state – no error, only in
start phase
---
System in "Stop" (PREOP)
state – no error, only in
start phase
5 Operation
Diagnos-
Recommended action
tics with
Setup pro-
Use the setup program
gram or
to determine which
Web
module is incompatible;
browser
replace module, or load,
replace, or remove
optional board.
Perform firmware
update, observe ver-
sioning.
Manual for setup
program
B 705000.6
LED/setup
program
LED/setup
program
Buffer battery is dead or
almost dead;
replace buffer battery.
Re-transfer configura-
tion with the setup pro-
gram.
LED
LED
LED
43