6 Configuration
6.11.4
Basic status setpoints
Specific values can be specified for each of the program channels for when the program is not
running (basic status). This relates to all setpoint values, the tolerance band, and the 16 oper-
ating contacts.
These values are also used if the program generator has been configured as a fixed-setpoint
generator.
Setup dialog
Parameters
Parameter
Program channel 1 to 3 (setpoint values and operating contacts in basic status)
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Tolerance min.
Tolerance max.
Contact
1 to 16
100
Selection/settings
-99999 to 0 to +99999
-99999 to 0 to +99999
-99999 to 0 to +99999
-99999 to 0 to +99999
-99999 to 0 to +99999
-99999 to 0 to +99999
Not selected (empty)
Selected (checkmark)
Description
Setpoint value 1
Setpoint value 2
Setpoint value 3
Setpoint value 4
Minimum value of the tolerance band
Maximum value of the tolerance band
Operating contact not active
Operating contact active