JUMO mTRON T Operating Manual page 72

Measuring, control, and automation system central processing unit
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

6 Configuration
Parameter
Actual value
Setpoint value
Acknowledgem.
Acknowledg.
signal
Hysteresis
function
?
Start-up alarm
suppression
?
Limit value
Switching
differential
Switch-on delay
Switch-off delay
Pulse time
72
Selection/settings
Analog signal as actual value (signal to be monitored)
Inactive
Module (source of the analog signal)
Analog signal as setpoint value (reference signal for AF1 to AF6)
Inactive
Module (source of the analog signal)
Condition for acknowledgement of the output signal (self-maintaining)
OFF
If inactive
Always
Signal to acknowledge the output signal
Inactive
Module (source of signal)
Switching differential position around the limit value
Symmetric
Asymmetric left
Asymmetric right
Inactive
Active
-3.37E+38 to 0 to +3.37E+38
0 to 1 to 99999
0 to 65535 s
0 to 65535 s
0 to 65535 s
Description
No signal selected.
The analog signal must be selected in
the following field (analog selector).
No signal selected.
The analog signal must be selected in
the following field (analog selector).
No acknowledgement required (output
signal is deactivated automatically if the
alarm condition is no longer present).
Acknowledgement only possible if alarm
condition is no longer present.
Acknowledgement always possible
No signal selected.
Acknowledgement by means of a signal
(high active) that must be selected in the
following field (digital selector).
Switching differential is positioned with
half above and half below the limit value.
Switching differential below the limit
value (typically)
Switching differential above the limit
value (typically)
Limit value monitoring always operates
according to its alarm function.
No alarm after power on or if limit value
or setpoint value is changed
Admissible deviation of the actual value
Switching thresholds of the output signal
(difference from limit value)
Delay time for activation of the output
signal if alarm condition is present.
Delay time for deactivation of the output
signal if alarm condition is no longer
present.
Output signal is deactivated automati-
cally after this time.