JUMO mTRON T Operating Manual page 94

Measuring, control, and automation system central processing unit
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

6 Configuration
Parameters
Parameter
Function
Start program
Behavior at
O-o-R
Power off
?
94
Selection/settings
Without function
Program generator
Fixed-setpoint generator
Program start
Actual value
Time
Behavior of the program generator if measurement range is exceeded or if there is
measuring range underflow (Out-of-Range)
Continuous operation
Program stop
Behavior of the program generator when the power failure is over.
Abort
Continuous operation
Standstill
Proceed at x %
Proceed at actual value
Description
Program generator is switched off.
Program generator is controlled by a
program.
The program generator operates as a
fixed-setpoint generator. In this case,
the setpoint values for the basic status
or manual mode are used.
Program starts at the first programmed
setpoint value.
The actual value of program channel 1
is adopted as the first setpoint value. All
other channels run synchronously from
this point in time.
A start time specified for program start is
adopted as the start time in a 24 h pro-
gram.
Example:
Start time: 06:00:00; 24 h program from
00:00 to 24:00: The program starts at 6
a.m. and runs until midnight.
Program continues to run.
Program is stopped.
Program is aborted; the program gener-
ator enters basic status.
Program continues running to the point
that it was at when the power failed.
Program is stopped; the program gener-
ator enters basic status.
The program can be set to continue or
abort.
If the difference of the actual value
before and after the power failure is
below or equal to x %, the program con-
tinues running to the point that it was at
when the power failed. If this is not the
case, the program generator enters
standstill.
The program continues running at the
actual value; consideration is given to
whether the program profile had a posi-
tive or negative trend at the time of the
power failure.

Advertisement

Table of Contents
loading

Table of Contents