Advertisement

5 Operation
5.2

System states

The following characteristics indicate the various system states:
"Run" system state
To achieve this state, use the system switch (Run) or the setup program;
if there is an error in a mandatory module, the system does not enter the "Run" state.
Requirement: the system must not be in the "Init" state.
Input values are adopted by the system; outputs are actuated (are active).
Interfaces (Com1 and Com2) are active.
The system switch, setup program, or PLC can be used for changeover to "Stop".
The setup program can be used to transfer the configuration; here the user can make the
adjustment whether the system is set to the safe "Stop" state beforehand.
Software update is possible, but the system is set to "Stop" automatically.
"Stop" system state
To achieve this state, use the system switch (Stop), setup program, or PLC.
Requirement: the system must not be in the "Init" state.
Input values are adopted by the system; outputs are switched off (inactive).
Modules are in safe state (except independent controller modules).
Interfaces (Com1 and Com2) are active.
The setup program can be used for changeover to "Run", provided this is not prevented by
the "Stop" switch setting.
The setup program can be used to transfer the configuration.
Recording function continues to run, default values are used in part.
Software update is possible.
Three-step controller in manual mode: control element can still be operated, provided com-
munication with the multifunction panel is available.
"Init" system state
To achieve this state, use the system switch ("Origin" reset).
Outputs are switched off (inactive).
Modules are in safe state (except independent controller modules).
Interfaces (Com1 and Com2) are active.
Changeover to "Run" and "Stop" is not possible using the setup program or PLC.
System startup must be performed with the setup program.
Recording function continues to run; analog inputs of the multifunction panel are set to de-
fault values.
PLC program and all internal PLC memory areas are deleted; PLC is set to original state.
"Calibration mode" system state
Activation in setup program using the "Calibrate / test" function (online parameter) for the
relevant module
The entire system enters calibration mode.
PLC in "Stop" state; system bus in "Run" state (outputs are actuated)