Up to 100 icons are available in a pool. The following screenshot shows a list of the icons avail-
able by default, with a preview image for the selected icon.
"Replace" button: The selected icon is replaced by different icon, which must be selected from
a file directory as a graphic in BMP format (max. 32 × 32 pixels; 256 colors). During this pro-
cess, the name that is used for the icon in the list can be changed so that it is different to the
file name. If the "Transparent import" option is active (checkbox selected), white areas in the
icon become transparent in the multifunction panel.
"Export" button: The selected icon is saved in a file directory as a graphic in BMP format.
Repetition
A program is completely repeated only after the expiry of the longest channel. The setpoint val-
ues of the longest channel jump from the value in the last section to the value in the first section,
regardless of the specification (step or ramp).
The setpoint values in those channels with shorter runtime move to basic status after the chan-
nel has expired. At the beginning of the repetition, the setpoint values jump to the values of the
first section.
Repetitions of program sections are executed even when a program is repeated.
Temporary changes during a program run will be also performed during the following program
repetitions. Program repetitions cannot be changed temporarily.
A delayed program start affects only the first program run and does not affect the program rep-
etition. The end signal becomes active when all repetitions are over.
The signal for batch control is activated at program start and remains active until the last pro-
gram repetition is finished or until the program is aborted manually.
Running program repetitions are maintained after a power failure and will processed at the
point at which the power failure occurred. If program channel 1 is already elapsed before the
power failure occurs while other program channels are still running, then, after the power failure
is over, the program starts at the beginning of the program and the cycle counter is increased
by 1.
Allocation
To execute a program, at least one program generator must be selected. A program can be
executed via up to 9 program generators at the same time.
The setpoint values are checked for compliance with the input limits of all selected program
generators (even if temporarily entered).
If multiple programs are executed at the same time, these must be assigned different program
generators.
9 Program editor
135